CleaverBrooks CBT Operation And Maintenance Manual page 25

Tubeless vertical boiler
Table of Contents

Advertisement

Gas Piping
MANUAL SHUTOFF
VALVE
Pipe sizing for multiple unit manifolds
TABLE 2- 6.
CBT 10 HP boilers
# of
1
Units
Pipe Size
1-1/4"
To Boiler
Header
1-1/2"
Pipe Size
TABLE 2- 8.
CBT 20 HP boilers
# of
1
Units
Pipe Size
1-1/2"
To Boiler
Header
1-1/2"
Pipe Size
TABLE 2- 10.
CBT 30 HP boilers
# of
1
Units
Pipe Size
2"
To Boiler
Header
2"
Pipe Size
750-382
CBT
REGULATOR (OPTIONAL)
BY INSTALLER
FIGURE 2-5.
Typical gas piping - Example 2
2
3
4
1-1/4"
1-1/4"
1-1/4"
1-1/2"
2"
2"
2
3
4
1-1/2"
1-1/2"
1-1/2"
2"
2-1/2"
2-1/2"
2
3
4
2"
2"
2"
2-1/2"
3"
3"
MANUAL SHUTOFF
VALVE
STRAINER
DRIP LEG REQUIRED FOR ANY VERTICAL RUN OF PIPING
TABLE 2- 7.
CBT 15 HP boilers
# of
1
Units
Pipe Size
1-1/4"
1-1/4"
To Boiler
Header
1-1/2"
Pipe Size
TABLE 2- 9.
CBT 25 HP boilers
# of
1
Units
Pipe Size
1-1/2"
1-1/2"
To Boiler
Header
1-1/2"
Pipe Size
GAS HEADER - SIZE FOR BOILER ROOM
CAPACITY AND TO MINIMIZE PRESSURE LOSS
2
3
4
1-1/4"
1-1/4"
2"
2"
2-1/2"
2
3
4
1-1/2"
1-1/2"
2"
2-1/2"
3"
2-9