Eaton Matrix 2000 Installation And Operation Manual page 25

Hide thumbs Also See for Matrix 2000:
Table of Contents

Advertisement

A
p
p
e
n
d
i
x
A
Specific ati ons
DC Input
Connector
Nominal voltage
Operating range
Maximum input current
Under voltage warning threshold
Under voltage threshold
Over voltage warning threshold
Over voltage threshold
Inrush current
Isolation DC-enclosure
Input protection
Psophometric noise voltage
Wide Band Noise
Peak to peak noise
AC Input (with Transfer Switch)
Connector
Voltage Range
Frequency Range
Nominal input current (maximum)
Over Voltage Threshold
Under Voltage Threshold
Transfer Time
120V models:
230V models:
Copyright © 2017 Eaton Corporation. All Rights Reserved.
IPN 997-00012-72C
Specifications
1/4" studs, 5/8" spacing to suit 2-hole crimp lugs
(not included)
48V dc
40 – 60V dc
56A
45V dc
40V dc
58V dc
60V dc
<2*I
rated
707V dc (Varistors and filter capacitor
removed)/1min
Reverse Polarity Protection
≤1.0mV ITU-T O.41 (16.66 ~ 6000Hz)
<1.0mV psof (25Hz~5kHz)
<20mV rms (25Hz~20kHz)
150mV up to 100MHz
Cord (2.2m/7 ft) with NEMA 5-20P
IEC 320-C20 plug to suit IEC 320-C19 socket (not
included)
110/115/120V ac:
208/220/230/240V ac:
50/60Hz ± 2.5%
110/115/120V ac:
208/220/230/240V ac:
138/276V ac
89/176V ac
Inverter to utility ac:
Utility ac to inverter:
July 2017
Appendix A
89 – 138V ac
176 – 276V ac
19A
10A
8ms
10ms
19