Redback® A 4500A Evac Controller & Timer
3.3 A 4578 and A 4581 Remote Plates
The A 4578 and A 4581 wall plates allow a remote means of triggering the Alert, Evacuation and Bell (A 4581 only) tones
and the cancel function. The switches are momentary operation and must be pressed for up to 3 seconds to activate. The
switches have protective "flip up" covers to prevent accidental operation.
Connection is made to the A 4500A via standard Cat5e cabling as shown in Fig 3.3 and Fig 3.4 There are two RJ45 ports
on the rear of the wall plates, either of which can be used. If the A 4578 or A 4581 has a connection problem with the
A 4500A main unit, the LED on the wall plate will flash.
Only one A 4578 or A 4581 wall plate is allowed to be connected to the A 4500A via the RJ45 port.
A 4578
24V
24V
DC FUSE
DC In
DC In
-
+
(1A M205)
24V
24V
DC FUSE
DC In
DC In
-
+
(1A M205)
22
Redback® Proudly Made In Australia
A 4578 Remote
Wall Plate
Common
IMPORTANT NOTE
24V Out
24V Out
Ensure power is switched o when
adjusting DIP switches. New
settings will be e ective when
Cancel
Evac
Alert
Bell
power is switched back on.
Trigger
Trigger
Trigger
Trigger
DIP Switches
1
2
3
4
5
6
7
8
1 2 3 4 5 6 7 8
Outputs limited to 120mA maximum current draw
A 4581 Remote
Wall Plate
Common
Evac
IMPORTANT NOTE
Ensure power is switched o when
24V Out
24V Out
adjusting DIP switches. New
settings will be e ective when
Cancel
Evac
Alert
Bell
power is switched back on.
Trigger
Trigger
Trigger
Trigger
DIP Switches
1
2
3
4
5
6
7
8
1 2 3 4 5 6 7 8
Outputs limited to 120mA maximum current draw
A 4581
Alert
Evac
Cancel
Master unit in manual mode (Plate Inactive)
CAT5e cable
(Max 300 Metres)
DIP SWITCH SETTINGS
Evac
Alert
Bell
SW
ON
OFF
SW
24V Out
24V Out
1
2
Loop PreBell/Bell Until Cancelled Play Prebell/Bell Once
3
4
Disable Menu Options
Enable Menu Options
5-8
NOT USED
Battery
Backup
Interface 1
Master unit
in manual
mode.
(Plate
Alert
Evac
Inactive)
Chime
Cancel
CAT5e cable
(Max 300 Metres)
DIP SWITCH SETTINGS
Alert
Bell
SW
ON
OFF
SW
24V Out
24V Out
1
Loop PreBell/Bell Until Cancelled Play Prebell/Bell Once
2
3
4
Disable Menu Options
Enable Menu Options
5-8
NOT USED
Battery
Interface 1
Backup
Rear of plate
Fig 3.3
ON
OFF
Voice Over Enabled
Voice Over Disabled
Disable Isolate Switch
Enable Isolate Switch
Alert/Evac
Bell
Music
V/Over
Prebell
Level
Level
Level
Level
Level
ON
OFF
Audio
Out
Fig 3.4
ON
OFF
Voice Over Enabled
Voice Over Disabled
Disable Isolate Switch
Enable Isolate Switch
Alert/Evac
Bell
Music
V/Over
Prebell
Level
Level
Level
Level
Level
ON
OFF
Audio
Out
www.altronics.com.au
Setup
L
R
Manufactured in Australia
By Altronic Distributors Pty. Ltd.
www.redbackaudio.com.au
L
R
Manufactured in Australia
By Altronic Distributors Pty. Ltd.
www.redbackaudio.com.au