A 2081 Remote Plate - Redback A 2078B Operating Manual

Alert/evacuation controller and 50 event timer, alert/evac/cancel remote wall plate, alert/evac/chime/cancel remote wall plate, alert/evac/cancel remote wall plate, alert/evac/chime/cancel remote wall plate
Hide thumbs Also See for A 2078B:
Table of Contents

Advertisement

Setup

3.2 A 2081 Remote Plate

The A 2081 wall plate provides a remote means of triggering the Alert, Evacuation and Bell tones and the cancel function.
Connection is made to the A 4500A via a minimum of 9 wires as shown in Fig 3.2B.
If standard Cat5 cable is used for the wiring, the plate can be located up to 30m away from the main unit. This can be
increased to 100m away using heavier guage cable, which reduces the voltage drop across this distance and ensures the
switch leds illuminate.
www.altronics.com.au
Redback® A 4500A Evac Controller & Timer
The Alert/Evac/Chime/Cancel switches on the A 2081 wall plate
are connected to the corresponding contacts on the rear of the
A 4500A. While the Alert,Evac and Bell leds on the wall plate
are connected to the Alert,Evac and Bell 24V outputs of the A
4500A. The cancel led is not connected. A mimimum of nine
wires can be used if the ground connections of the Alert,Evac
and Bell 24V outputs are linked and if the Alert/Evac/Chime and
cancel switch grounds are linked together (see Fig 3.2B).
Fig 3.2A
A 4500A 50 EVENT TIMER
Cancel
Evac
Alert
Bell
Trigger
Trigger
Trigger
Trigger
a c
E v
Cancel
Chime
Evac
Alert
Switch
Switch
Switch
Switch
l
c e
a n
C
A 2081 REMOTE WALL PLATE
Fig 3.2B
Common
Evac
Alert
24V Out
24V Out
24V Out
24V Out
Outputs limited to 120mA maximum current draw
t
e r
A l
- + - +
- +
Chime
Evac
Alert
Lamp
Lamp
Lamp
e
m
h i
C
Redback® Proudly Made In Australia 21