WEBs CIPer MODEL 50 – USER GUIDE

Order numbers (SKU)

The onboard HMI is featured in the below listed order numbers:
WEB-EAGLENX26D
WEB-EAGLENX26ND
IMPORTANT:
To make efficient use of HMI functionality, it is required to do a few set-up steps in Honeywell WEBStation
N4.4.93.40.8 or higher. Refer section "HMI configuration principles" given below.
WEB-EAGLENX26D
The XL2000HMI can be connected and operated with the below listed OS (SKU) numbers.
WEB-EAGLENX26ND

HMI configuration principles

To get the onboard HMI or detached HMI operational, the following configuration principles need to be done
in WEBs N4:
1. Add & enable the HMI Service.
2. Set the PIN for the HMI access.
3. Add HMI and LED Alarm recipients.
NOTE: As long as there are un-acknowledged alarms in the station, the alarm symbol will be blinking,
regardless if a user is logged-in to the HMI or not. See below picture:
4. Configure the alarming for the HMI.
5. Fill the Fast Access Lists (FAL) with data-points, schedules & parameters.
6. If desired, create a custom HMI sequence.
31-00198—01
4