Onboard Inputs And Outputs - Honeywell CIPer 50 User Manual

Table of Contents

Advertisement

WEBs CIPer MODEL 50 – USER GUIDE

Onboard Inputs and Outputs

Onboard
Inputs/Outputs
Description
NTC10kΩ (Type II), NTC20kΩ,
0...10V, slow BI 0.4 Hz
Short-circuit protected against
UI
24VAC
(Universal
NTC10kΩ (Type II), NTC20kΩ,
Input)
0...10V fix pull-up, slow BI 0.4 Hz
Short-circuit protected against
24VAC
open = 24 VDC, closed 2.0 mA,
BI
totalizer @ 15 Hz max.
(Binary Input)
Short-circuit protected against
24VAC
AO
0..11 V (max. 1 mA)
(Analog Output)
Relay Normally Open contact 3A,
250VAC, 30VDC
BO
Relay Normally Open contact 10A,
(Binary Output)
250VAC, 30VDC
Relay Normally Open contact with
one common
For all technical details on Onboard Inputs/Outputs, please refer to the CIPer 50 Product Datasheet
(31-00197-01) and CIPer 50 Installation & Commissioning Instructions (31-00233EFS).
31-00198—01
Max.
cable
WEB-
length
EAGLENX26D
1200 ft
1200 ft
1200 ft
1200 ft
1200 ft
1200 ft
1200 ft
16
WEB-
EAGLENX26ND
8
8
2
2
4
4
4
4
4
4
1
1
3
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents