APPENDIX-C: TROUBLESHOOTING

DEFINITIONS FOR EVENT HISTORY ENTRIES
A. General
ENTRY
Disabled
Ground
Open
Short
Overload
GeneralTrouble
Unconfig
TypeMismatch
CommunicationTrouble
Multiple Device Response
TypeUnknown
Dirty
Replace
ParameterError
AddressInvalid
AddressUnspecified
ACFail
MessageLost
FatalFault
VoltageLow
VoltageHigh
OverCurrent
CircuitTrouble
BatteryAbsent
B. System Events
ENTRY
Reset
Silence
Unsilence
Test
QuitTest
Acknowledge
Unacknowledge
LogIn
LogOut
INDICATES
The device has been disabled
The device is in ground fault
The device is in open trouble
The device is in short trouble
The SLC line is overloaded
The device reports general trouble
The system finds a SLC device that is not in the config file
The SLC device type is not consistent with the config file
The communication between the device and the panel is abnormal
More than one SLC device has the same address
The device type is unknown to the panel
The SLC device is dirty
The SLC device needs to be replaced
The SLC device has invalid parameter setting
The address of SLC device is invalid
The SLC device has no address
The AC power of the system is in trouble
The DACT lost some messages because of limited memory space
The SLC device reported fatal fault trouble
The battery voltage is too low
The battery voltage is too high
The NAC is in over current state
The battery charge circuit is in trouble
The battery is missing
INDICATES/NOTES
Panel reset
Silence all silenceable outputs
Unsilence all silenced outputs
Start quick test
Exit quick test
Panel events acknowledged
Resound of the trouble/supervisory
User level login
User level logout
55