Battery Size Calculations; System Current Draw Break Down; Slc Current Draw Break Down - Siemens FC901-U3 Installation, Operation And Maintenance Manual

Fire alarm control panel
Hide thumbs Also See for FC901-U3:
Table of Contents

Advertisement

BATTERY SIZE CALCULATIONS

System Current Draw Break down

System Current Draw Components
Main board
NAC
SLC
Auxiliary power
City tie module

SLC Current Draw Break down

SLC Current Draw Components
HFP-11 / 8713
HFPO-11 / 8710
HFPT-11 / 8712
OOHC941
OOH941
OH921
OP921
HI921
FDCIO42
HMS / 8700 -S/D/M
HTRI-S / 8702
HTRI-D / 8703
HTRI-R / 8704
HZM / 8705
HCP /8706
ILED / 8726
FDOOTC441
FDOOT441
FDOT421
FDO421
FDT421
ABHW-4B
ABHW-4S
Total Standby Current = 0.1590 + C2 + C4 + 0.0017(if used)
Total Alarm Current = 0.1864 + C1 + C3 + C5 + 0.0158(if used)
Where
C1 = NAC1 current + NAC2 current, should be less or equal to 2.5A.
C2 = ∑quantity of each type of detector x standby current/each
C3 = ∑quantity of each type of detector x alarm current/each
C4 = External device current draw through Aux1 and Aux2 in standby stage, either one of
Aux1 and Aux2 should be less than or equal to 0.75A.
C5 = External device current draw through Aux1 and Aux2 in alarm stage, either one of Aux1
and Aux2 should be less than or equal to 0.75A.
Standby(A)
0.1590
0
C2
C4
0.0017
Standby(A)
0.00140
0.00140
0.00140
0.00075
0.00068
0.00030
0.00030
0.00028
0.00120
0.00140
0.00140
0.00140
0.00140
0.00140
0.00140
0.00140
0.00075
0.00068
0.00030
0.00030
0.00028
0.00030
0.00030
50
Alarm(A)
0.1864
C1
C3
C5
0.0158
Alarm(A)
0.00140
0.00140
0.00140
0.00075
0.00068
0.00030
0.00030
0.00028
0.00120
0.00140
0.00140
0.00140
0.00140
0.00140
0.00140
0.00140
0.00075
0.00068
0.00030
0.00030
0.00028
0.00030
0.00030