Maintenance; General - Siemens FC901-U3 Installation, Operation And Maintenance Manual

Fire alarm control panel
Hide thumbs Also See for FC901-U3:
Table of Contents

Advertisement

MAINTENANCE

GENERAL

The FC901 provides maintenance functions to allow for the setting and controlling of various
features in the system.
The maintenance functions are protected by a four digit password. To access the maintenance
features press the "MENU" button and select Login item in the View menu, enter the four digit
code when prompted and then press "OK".
FC901 Maintenance is separated into two levels. The user can enter a different password to
enter different levels.
Level 2: Protected by level 2 password, Level 2 provides control functions.
Level 3: Protected by level 3 password, Level 3 provides control functions and parameter
change functions.
The following functions are accessible to L2 and L3 user by selecting items in the Operate
menu.
Disable/Enable Devices
Disable/Enable NACs
Disable/Enable City Tie
Disable/Enable DACT
Disable/Enable Status Relays
Disable/Enable Detector Applications
Disable/Enable PAS
Starting and Configuring Quick Test
Set the Time
Set the Date
The functions listed below are provided specifically to L3 users.
Edit Device Labels
Edit System Labels
Program a Device
Change the Maintenance Password
Disabling any input and output devices, applications will annunciate a trouble
condition.
46