De-Installing The Op; Tool: Metravision - t.a.c. Xenta OP Handbook

Table of Contents

Advertisement

TAC Xenta OP Handbook

2.7 De-installing the OP

2.7.1 Tool: MetraVision

Factory setting
TAC AB, 2001-08-08
If the OP is to be de-installed from the network, it should be restored
to the original factory setting to avoid problems, if used in another
network.
Depending on which binding tool has been used, the de-installation is
made according to one of the methods shown below.
1 Select OP Service menu – 10. OP mode and set
Bindable to "TAC" or, in OP version < 3.11, "OFF".
2 Disconnect the OP electrically from the network.
3 "Remove" the OP node from the data base.
If the OP has been labelled "Unconfig", which may happen if step 3
above was executed before step 2, or for any other reason; the OP may
be restored to the factory setting in one of two ways:
A
Reconnect the OP to the network, reinstall it and perform the steps
above in the correct order,
or,
B
use the Nodutil program and do the following.
1 Select OP Service menu – 10. OP mode and set
Bindable to "TAC" or, in OP version < 3.11, "OFF".
2 Start Nodutil.
3 Press the Service pin of the OP.
4 Type "G".
5 Type "1", press Enter.
6 Type "M".
7 Type "S".
8 Type "C".
2 Connection and Basic Functions