Safety regulations and installation notes

5.1

Installation notes

WARNING:
Observe the following safety notes when using
the FO converter.
The category 3 device is suitable for installation in
Zone 2 potentially explosive areas. It meets the require-
ments of EN 60079-0:2012+A11:2013 and EN 60079-
15:2010.
Installation, operation, and maintenance may only be
carried out by qualified electricians. Follow the installa-
tion instructions as described. When installing and op-
erating the device, the applicable regulations and
safety directives (including national safety directives),
as well as the general codes of practice, must be ob-
served. The safety data is provided in the packing slip
and on the certificates (conformity assessment, addi-
tional approvals where applicable).
The device must not be opened or modified apart from
the configuration of the DIP switches. Do not repair the
device yourself; replace it with an equivalent device in-
stead. Repairs may only be carried out by the manufac-
turer. The manufacturer is not liable for damage
resulting from non-compliance.
The IP20 degree of protection (IEC 60529/EN 60529) of
the device is intended for use in a clean and dry envi-
ronment. Do not subject the device to mechanical
and/or thermal loads that exceed the specified limits.
This device is not designed for use in atmospheres with
a risk of dust explosions.
5.3

UL notes

103266_en_02
The switches of the device that can be accessed may
only be actuated when power to the device is discon-
nected.
The device is only intended for operation with SELV ac-
cording to IEC 60950/EN 60950/VDE 0805. The device
may only be connected to devices that meet the re-
quirements of EN 60950.
5.2

Installation in zone 2

WARNING: Explosion hazard when used in
potentially explosive areas
Make sure that the following notes and instruc-
tions are observed.
Observe the specified conditions for use in potentially
explosive areas!
Install the device in a suitable, approved housing (with
at least IP54 protection) that meets the requirements of
EN 60079-15. For this purpose, observe the require-
ments of IEC 60079-14 / EN 60079-14.
Only connect devices to the supply and signal circuits in
zone 2 that are suitable for operation in Ex zone 2 and
for the conditions at the installation location.
In potentially explosive areas, only snap the device onto
or off the DIN rail connector and connect/disconnect ca-
bles when the power is disconnected.
The device must be stopped and immediately removed
from the Ex area if it is damaged, was subjected to an
impermissible load, stored incorrectly or if it malfunc-
tions.
Connection to the D-SUB interface is only permitted if
the screw connection is tightened.
PSI-MOS-RS232/FO 1300 E
7 / 17