Fantech VLT 2800 Series Instruction Manual page 93

Table of Contents

Advertisement

- AC line voltage too high.
ALARMS 37-45: Internal faults
ALARM 37: Internal fault number 0
Communication fault between control card and BMC2.
ALARM 38: Internal fault number 1
Flash EEPROM fault on control card.
ALARM 39: Internal fault number 2
RAM fault on control card.
ALARM 40: Internal fault number 3
Calibration constant error in EEPROM.
ALARM 41: Internal fault number 4
Data values error in EEPROM.
ALARM 42: Internal fault number 5
Fault in motor parameter database.
ALARM 43: Internal fault number 6
General power card fault.
ALARM 44: Iinternal fault number 7
Minimum software version of control card or BMC2.
ALARM 45: Internal fault number 8
I/O fault (digital input/output, relay or analog
input/output).
NOTE
When restarting after an alarm 38-45,
the VLT adjustable frequency drive will
display an alarm 37. In parameter 615 the
actual alarm code can be read.
Alarm/warning limits:
VLT 2800
Undervoltage
Voltage warning low
Voltage warning high
Overvoltage
The voltages stated are the intermediate circuit
voltage of the frequency converter with a tolerance
92
Without brake
With brake
1 / 3 x 200 - 240 V
1 / 3 x 200 - 240 V
[VDC]
[VDC]
215
215
230
230
385
400
410
410
VLT® 2800 Series
ALARMS 50-56: AMT faults
ALARM 50: AMT not possible
One of the following three possibilities can occur:
- The calculated R
value falls outside permitted limits.
S
- The motor current in at least one of the
motor phases is too low.
- The motor in use is too small for AMT
calculations to be performed.
ALARM 51: AMT Fault re. nameplate data
There is inconsistency in the registered motor data.
Check the motor data for the relevant setup.
ALARM 52: AMT faulty motor phase
The motor current in at least one of the motor
phases is too low.
ALARM 55: AMT timeout
The calculations are taking too long, possibly
due to noise in the motor cables.
ALARM 56: AMT warning during AMT
An adjustable frequency drive warning is given
while AMT is being performed.
WARNING 99: Locked
The control panel functions have been locked
via parameter 018.
Without brake
3 x 380 - 480 V
[VDC]
410
440
765
820
of ± 5 %. The corresponding line voltage is the
intermediate circuit voltage divided by 1.35.
MG.28.A8.22 - VLT is a registered Danfoss trademark
With brake
3 x 380 - 480 V
[VDC]
410
440
800
820

Advertisement