Programming; Operation & Display - Fantech VLT 2800 Series Instruction Manual

Table of Contents

Advertisement

Operation & Display
001 Language
(LANGUAGE)
Value:
English (ENGLISH)
German (DEUTSCH)
French (FRANCAIS)
Danish (DANSK)
Spanish (ESPANOL)
Italian (ITALIANO)
Function:
This parameter is used to choose the language
to be shown in the display whenever the LCP
control unit is connected.
Description of choice:
There is a choice of the languages shown. The
factory setting may vary.
002 Local/remote operation
(OPERATION SITE)
Value:
Remote operation (REMOTE)
Local operation (LOCAL)
Function:
There is a choice of two different modes of operation
of the variable frequency drive. Remote operation [0]
or Local operation [1]. See also parameter 013 Local
control if Local operation [1] is selected.
Description of choice:
If Remote operation [0] is selected, the variable
frequency drive is controlled via:
1. the control terminals or via serial communication.
2. the [START] key. This cannot, however, override
stop commands transmitted via the digital inputs
or via serial communication.
3. the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
If Local operation [1], is selected, the variable
frequency drive is controlled via:
1. the [START] key. This cannot, however, override
stop commands via the digital inputs (see
parameter 013 Local control).
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark
VLT® 2800 Series
2. the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
3. the [FWD/REV] key, on the condition that is has
been selected as active in parameter 016 Local
reversing, and that parameter 013 Local control
is set at Local control and open loop [1] or Local
[0]
control as parameter 100 [3]. Parameter 200
[1]
Output frequency range is set at Both directions.
[2]
4. parameter 003 Local reference where the reference
[3]
can be set using the [+] and [-] keys.
[4]
5. an external control command that can be
[5]
connected to the digital inputs (see parameter
013 Local control).
NOTE
The [JOG] and [FWD/REV] keys are located
on the LCP control unit.
003 Local reference
(LOCAL REFERENCE)
Value:
Par.013 Local control must be set to [1] or [2]:
0 - f
(par. 202)
MAX
[0]
Par. 013 Local control must be set to [3] or [4] and
[1]
parameter 203 Reference/feedback range to [0]:
Ref
- Ref
MIN
MAX
Par. 013 Local control must be set to [3] or [4] and
parameter 203 Reference/feedback range to [1]:
- Ref
- + Ref
MAX
Function:
In this parameter, the local reference can be set
manually. The unit of the local reference depends on the
configuration selected in parameter 100 Configuration.
Description of choice:
In order to protect the local reference, parameter
002 Local/remote operation must be set to
Local operation [1]. Local reference cannot be
set via serial communication.
000,000.000
(par. 204-205)
000,000.000
(par. 204-205)
000,000.000
MAX
31