Fantech VLT 2800 Series Instruction Manual page 82

Table of Contents

Advertisement

515-544 Data readout
Value:
Par.
Description
no.
515
Res. reference
516
Res. reference [Unit]
517
Feedback [Unit]
518
Frequency
519
Frequency x scale
520
Motor current
521
Torque
522
Power[kW]
523
Power[HP]
524
Motor voltage
525
DC-link voltage
526
Thermal load motor
527
Thermal load inverter
528
Digital input
529
Term.53, analog input
531
Term.60, analog input
532
Pulse reference
533
External ref.
534
Status word, Hex
535
Bus feedback 1
537
Inverter temperature
538
Alarm word
539
Control word
540
Warning word
541
Extended status word
544
Pulse count
Function:
These parameters can be read out via the serial
communication port and the LCP display. See also
parameters 009-012 Display readout.
NOTE
Parameters 515-541 can only be read out
via an LCP control unit.
Description of choice:
Parameter 515, Resulting reference %:
Gives the resulting reference as a percentage in the
range from Minimum reference, Ref
reference, Ref
. See also Handling of References.
MAX
Parameter 516, Resulting reference [unit]:
Gives the resulting reference in Hz in closed loop
(parameter 100). In closed loop the reference unit
in parameter 416 Process units is selected.
Parameter 517, Feedback [unit]:
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark
Display text
(REFERENCE %)
(REFERENCE [UNIT])
(FEEDBACK [UNIT])
(FREQUENCY)
(FREQUENCY X SCALE)
(MOTOR CURRENT)
(TORQUE)
(POWER (KW))
(POWER (HP))
(MOTOR VOLTAGE)
(DC LINK VOLTAGE)
(MOTOR THERMAL)
(INV. THERMAL)
(DIGITAL INPUT)
(ANALOG INPUT 53)
(ANALOG INPUT 60)
(PULSE REFERENCE)
(EXT. REF.%)
(STATUS WORD)
(BUS FEEDBACK1)
(INVERTER TEMP.)
(ALARM WORD)
(CONTROL WORD)
(WARN. WORD)
(STATUS WORD)
(PULSE COUNT)
Gives the resulting feedback value with the unit/scaling
that is selected in parameters 414, 415 and 416.
See also handling of feedback.
Parameter 518, Frequency [Hz]:
Gives the output frequency from the adjustable
frequency drive.
Parameter 519, Frequency x scaling [-]:
Corresponds to the present output frequency f
multiplied by the factor preset in parameter 008
Display scaling of output frequency .
to Maximum
Parameter 520, Motor current [A]:
MIN
Gives the motor's phase current measured
as an effective value.
Parameter 521, Torque [Nm]:
Gives the motor's present load in relation to
the motor's rated torque.
Parameter 522, Power [kW]:
VLT® 2800 Series
Unit
%
Hz, rpm
Par. 416
Hz
Hz
Amp
%
kW
HP
V
V
%
%
Bin
V
mA
Hz
%
Hex
Hex
°C
Hex
Hex
Hex
Hex
Update
interval