Use the following procedure for the control card test:
1. Select control card test.
2. Disconnect the AC line voltage and wait until the
light in the display has disappeared.
3. Mount according to drawing and description.
4. Connect the AC line voltage.
5. The adjustable frequency drive automatically
undertakes a test of the control card.
If the adjustable frequency drive displays a fault code
from 37-45, the control card test has failed. Change the
control card to start up the adjustable frequency drive.
If the adjustable frequency drive comes into Display
mode, the test is OK. Remove the test connector
and the adjustable frequency drive is ready for
operation. Parameter 620 Operating mode is
automatically set to Normal operation [0].
Initialization [3] is selected if you wish to use
the unit's factory setting.
Procedure for initialization:
1. Select Initialization [3].
2. Disconnect the AC line voltage and wait until the
light in the display has disappeared.
3. Connect the AC line voltage.
4. An initialization is performed in all parameters
in all Setups, with the exception of parameters
500 Address, 501 Baudrate, 600-605 Operating
data and 615-617 Fault log.
= factory setting. () = display text [] = value for use in communication via serial communication port
86
VLT® 2800 Series
MG.28.A8.22 - VLT is a registered Danfoss trademark