Resulting reference [%] gives, as a percentage,
the resulting reference in the range from Minimum
reference, Ref
to Maximum reference, Ref
MIN
Reference [unit] gives the resulting reference with unit
Hz in Open loop. In Closed loop the reference unit
is selected in parameter 416 Process units.
Feedback [unit] gives the resulting signal value
using the unit/scaling selected in parameter 414
Minimum feedback, FB
LOW
FB
and 416 Process units.
HIGH
Frequency [Hz] gives the output frequency of
the variable frequency drive.
Output frequency x scaling [-] equals the present output
frequency f
multiplied by the factor set in parameter
M
008 Display scaling of output frequency .
Motor current [A] gives the phase current of the
motor measured as an effective value.
Torque [%] denotes the motor's present load in
relation to the motor's rated torque.
Power [kW] gives the present power that the
motor is absorbing in kW.
Power [HP] gives the present power that the
motor is absorbing in HP.
Motor voltage[V] gives the voltage supplied to the motor.
DC link voltage [V] gives the intermediate circuit
voltage of the variable frequency drive.
Thermal load motor [%] gives the calculated/estimated
load on the motor. 100% is the cut-out limit.
Thermal load [%] gives the calculated/estimated
thermal load on the variable frequency drive.
100% is the cut-out limit.
Running hours [Hours] gives the number of hours that
the motor has tun since the last reset in parameter
619 Reset of running hours counter.
Digital input [Binary code] gives the signal status
from the 5 digital inputs (18, 19, 27, 29 and 33).
Terminal 18 corresponds to the bit on the extreme
left. '0' = no signal, '1' = signal connected.
Analog input 53 [V] gives the voltage value of terminal 53.
= factory setting. () = display text [] = value for use in communication via serial communication port
34
.
MAX
, 415 Maximum feedback,
VLT® 2800 Series
Analog input 60 [mA] gives the present value
of terminal 60.
Pulse reference [Hz] gives the reference in Hz
connected to terminal 33.
External reference [%] gives the sum of external
references as a percentage (sum of analog/pulse/serial
communication) in the range from Minimum reference,
Ref
to Maximum reference, Ref
MIN
Status word [Hex] gives one or several status
conditions in a Hex code. See Serial communication
in the Design Guide for further information.
Heatsink temp.[°C] gives the present heatsink
temperature of the variable frequency drive. The
cut-out limit is 195-212 °F (90-100°C), while cutting
back in occurs at 160 ± 5% (70 ± 5°C).
Alarm word [Hex] gives one or several alarms
in hex code. See Serial communication in the
Design Guide for further information.
Control word [Hex] gives the control word for the
variable frequency drive. See Serial communication
in the Design Guide for further information.
Warning word [Hex] gives one or several warnings
in hex code. See Serial communication in the
Design Guide for further information.
Extended status word [Hex] gives one or several status
modes in Hex code. See Serial communication in
the Design Guide for further information.
Communication option card warning [Hex] gives a
warning word if there is a fault in the communication
bus. Only active if communication options are installed.
If there are no communication options 0
Hex is displayed.
Pulse count gives the number of pulses that
the unit has registered.
MG.28.A8.22 - VLT is a registered Danfoss trademark
.