saved data value, and the highest log number
[10] contains the oldest data value.
Description of choice:
Read out as one value.
617 Fault log: Value
(F.LOG: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
In this parameter it is possible to see at which value a
trip occurred. The unit of the value depends on which
alarm is active in parameter 615 Fault log: Fault code .
Description of choice:
Read out as one value.
618 Reset of kWh counter
(RESET KWH COUNT)
Value:
No reset (DO NOT RESET)
Reset (RESET COUNTER)
Function:
Resetting parameter 602 kWh counter to zero.
Description of choice:
If Reset [1]is selected and you press the [OK]
key, the variable frequency drive's kWh counter
is reset to zero. This parameter cannot be
selected via serial communication.
NOTE
When the [OK] key is activated, the
counter is reset to zero.
619 RESET RUNNING HOURS COUNTER
(RESET RUN. HOUR)
Value:
No reset (DO NOT RESET)
Reset (RESET COUNTER)
Function:
Resetting of parameter 601 Hours run to zero.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark
VLT® 2800 Series
Description of choice:
If Reset [1] is selected and you press the [OK] key,
the variable frequency drive's parameter 601 is
reset to zero Hours run. This parameter cannot
be selected via serial communication.
NOTE
When the [OK] key is activated the
parameter is reset to zero.
620 Operation Mode
(OPERATION MODE)
Value:
Normal operation (NORMAL OPERATION)
Control card test (CONTROL CARD TEST)
Initialize (INITIALIZE)
Function:
In addition to its normal function, this parameter
can be used to test the control card.
There is also the opportunity to perform an
initialization at the factory setting for all parameters
in all Setups, with the exception of parameters
500 Address, 501 Baudrate, 600-605 Operating
[0]
data and 615-617 Fault log.
[1]
Description of choice:
Normal function [0] is used for normal
operation of the motor.
Control card test [2] is selected if you wish to check
the control card's analog/digital inputs, analog/digital
outputs, relay outputs and 10 V and 24 V voltages.
The test is performed as follows:
27 - 29 - 33 - 46 are connected.
50 - 53 are connected.
42 - 60 are connected.
12 - relay terminal 01 is connected.
18 - relay terminal 02 is connected.
19 - relay terminal 03 is connected.
See also the DeviceNet manual MG.90.BX.YY
for further details.
[0]
[1]
[0]
[2]
[3]
85