Technical Functions - Fantech VLT 2800 Series Instruction Manual

Table of Contents

Advertisement

Technical functions

600-605 Operating Data
Value:
Par. no.
Description
600
Operating hours
601
Hours run
602
kWh counter
603
Number of power-ups
604
Number of
overtemperatures
605
Number of overvoltages
Function:
These parameters can be read out via the serial
communication port and the LCP control unit.
Description of choice:
Parameter 600, Operating hours:
Gives the number of hours the adjustable frequency
drive has been operating. The value is saved
every hour and when there is an AC line failure.
This value cannot be reset.
Parameter 601, Hours run:
Gives the number of hours the motor has been
operating since the reset in parameter 619 Reset of
hours-run counter. The value is saved every hour
and when there is an AC line failure.
Parameter 602, kWh counter:
Gives the adjustable frequency drive's output energy
in kWh. The calculation is based on the mean kW
value over one hour. This value can be reset using
parameter 618 Reset of kWh counter.
Range: 0 - depends on unit.
Parameter 603, Number of power-ups:
Gives the number of power-ups of the supply voltage
undertaken on the adjustable frequency drive.
Parameter 604, Number of overtemperatures:
Gives the number of overtemperature faults
that have been registered on the adjustable
frequency drive's heatsink.
Parameter 605, Number of overvoltages:
Gives the number of overvoltages of the intermediate
circuit voltage in the adjustable frequency drive. This is
only counted when Alarm 7 Overvoltage is active.
= factory setting. () = display text [] = value for use in communication via serial communication port
84
VLT® 2800 Series
Display text
(OPERATING HOURS)
(RUNNING HOURS)
(KWH COUNTER)
(POWER UPS)
(OVER TEMPS)
(OVER VOLTS)
615 Fault log: Error code
Value:
[Index 1 - 10] Error code: 0 - 99
Function:
In this parameter it is possible to see the reason
for a trip (cut-out of the variable frequency drive)
occurring. 10 [1-10] log values are defined.
The lowest log number [1] contains the latest/most
recently saved data value. The highest log number [10]
contains the oldest data value saved. If a trip occurs,
it is possible to see the cause, time and a possible
value of the output current or output voltage.
Description of choice:
Given as a fault code, in which the number refers to a
table. See the table in Warnings/alarm messages.
616 Fault log: Time
Value:
[Index 1 - 10] Hours: 0 - 130,000.0
Function:
In this parameter it is possible to see the total number
of operating hours in connection with the last 10 trips.
10 [1-10] log values are denoted. The lowest
log number [1] contains the latest/most recently
Unit
Hours
Hours
kWh
Number of times
Number of times
Number of times
NOTE
Parameters 615-617 Fault log cannot be read
out via the integral control unit.
(F.LOG: ERROR COD)
(F.LOG: TIME)
MG.28.A8.22 - VLT is a registered Danfoss trademark
Range
0-130,000.0
0-130,000.0
Depends on unit
0-9999
0-9999
0-9999