Carel ir33+ Quick Start Manual

Carel ir33+ Quick Start Manual

Electronic controller for stand-alone refrigerating units
Hide thumbs Also See for ir33+:

Advertisement

Quick Links

+05Z0028EN- rel. 1.0 - 13.03.2014
ir33+
Electronic controller for stand-alone refrigerating units
Description:
ir33+* represent a range of electronic microprocessor controllers with LED
display developed for the management of stand-alone refrigerating units.
Part number list:
IREVM0LN0U, IREVM0EN0U
IREVS0LN0U, IREVS0EA0U,
IREVC0LN0U, IREVC0LC0U
IREVC0HN0U, IREVC0HC0U, IREVF0EN0U
Panel mounting
1
2
Rear (with 2 quick-fi t side brackets)
Dimensions (mm)
79.5
76.2
82
60
80.6
65
64
69
E, A Version
Buttons on the keypad
Button
Normal function
Pressing the button alone Pressing together with other buttons
PRG /
- if pressed for more than
PRG+ON-OFF/UP:
MUTE
3 s accesses the menu
if pressed together
for setting the password
for more than 3
to access the type "F"
s reset any alarm
(frequent) parameters or
with manual reset
"C" (Confi guration)
- in the event of alarm:
silences the audible alarm
(buzzer) and disables the
alarm relay
ON-OFF/
- if pressed for more than 3s
ON-OFF/UP+AUX/DOWN: if pressed together for
UP
disables the regulation / if
more than 3 s enable/disable the continuous cycle
pressed for more than 1s,
operation
enables the regulation
ON- OFF/UP+ SET/DEF: if pressed together for
- during the parameters
more than 3 s display the temperature read by the
modifi cation increase the
defrost probe no 1
value displayed move to-
ON-OFF/UP+ PRG/MUTE: if pressed together for
wards the next paramenter
more than 3 s reset any alarm with manual reset
AUX/
- if pressed for more than
AUX/DOWN + ON-OFF/UP: if pressed together for
DOWN
1 s, enables/disables the
more than 3 s enable/disable the continuous cycle
auxiliary output
operation
- during the parameters
AUX/DOWN + SET/DEF: if pressed together for more
modifi cation decrease the
than 1 s display a submenu with the HACCP alarm
value displayed or move
parameters (HA, HAn, HF, HFn)
towards the previous param.
SET/DEF - if pressed for more than 1s,
SET/DEF+ AUX/DOWN: if pressed together for more
enables/displays and/or
than 1 s display a submenu with the HACCP alarm
set the set point
parameters (HA, HAn, HF, HFn)
- if pressed for more than 5 s,
SET/DEF+ ON-OFF/UP: if pressed together for
enables a manual defrost
more than 3 s display the temperature read by the
defrost probe no 1
Table of alarms and signals: display, buzzer and relay
Code
Display icon
Alarm
Buzzer Reset
Description
relay
'rE'
ON
ON
automatic virtual control probe fault
+
fl ashing
'E0'
OFF
OFF
automatic room probe S1 fault
+
fl ashing
'E1'
OFF
OFF
automatic defrost probe S2 fault
+
fl ashing
'E2'-3-4
OFF
OFF
automatic probe S3-4-5 fault
+
fl ashing
'___'
no
OFF
OFF
automatic probe not enabled
'LO'
ON
ON
automatic low temperature alarm
fl ashing
'HI'
ON
ON
automatic high temperature alarm
fl ashing
'AFr'
ON
ON
manual
antifreeze alarm
fl ashing
'IA'
ON
ON
automatic immediate alarm from external
fl ashing
contact
'dA'
ON
ON
automatic delayed alarm from external contact
fl ashing
'dEF'
OFF
OFF
automatic defrost running
ON
'Ed1'-2 no
OFF
OFF
automatic/
defrost on evaporator 1-2 ended by
manual
timeout
'Pd'
ON
ON
automatic/
maximum time pump-down alarm
+
fl ashing
manual
'LP'
ON
ON
automatic/
low pressure alarm
+
fl ashing
manual
'AtS'
ON
ON
automatic/
autostart in pump-down
+
fl ashing
manual
'cht'
no
OFF
OFF
automatic/
high condenser temperature pre-
manual
alarm
'CHT'
ON
ON
manual
high condenser temperature alarm
+
fl ashing
'dor'
ON
ON
automatic door open for too long alarm
fl ashing
'Etc'
OFF
OFF
real time claock fault
fl ashing
'EE'
OFF
OFF
automatic EEPROM error, unit parameters
+
fl ashing
'EF'
OFF
OFF
automatic EEPROM error, operating parameters
+
fl ashing
'HA'
OFF
OFF
manual
HACCP alarm, type 'HA'
fl ashing
'HF'
OFF
OFF
manual
HACCP alarm, type 'HF'
fl ashing
'rCt'
signal
Instrument enabled for program-
ming from the remote control (not
available on ir33+)
'Add'
signal
Automatic address assignment
procedure in progress
'ccb'
signal
Request to start continuous cycle
'ccE'
signal
Request to end continuous cycle
'dFb'
signal
Request to start defrost
'dFE'
signal
Request to end defrost
'On'
signal
Switch ON
'OFF'
signal
Switch OFF
'rES'
signal
Reset alarms with manual reset;
Reset HACCP alarms; Reset tempera-
ture monitoring
'n1' . .. ' n6'
ON
ON
automatic Indicates an alarm on unit 1 to 6
fl ashing
present in the network
'dnL'
signal
Download in progress
'd1' . .. ' d6'
OFF
OFF
Download with errors on unit 1 to 6
fl ashing
Note: the buzzer is disabled if parameter 'H4 =1
Technical characteristics
power supply:
NO POWER
Model
Voltage
& SIGNAL
CABLES
IREVxxExxxx 230 V~, 50/60 Hz
TOGETHER
IREVxxHxxxx 115...230 V~, 50/60 Hz
READ CAREFULLY IN THE TEXT!
IREVxxLxxxx 12...24 V~, 50/60 Hz, 12...30 Vdc
Insulation guaranteed by the power supply:
IREVxxExxxx
insulation in reference to very low
IREVxxHxxxx
voltage parts
insulation from relay outputs
IREVxxLxxxx insulation in reference to very low
voltage parts
insulation from relay outputs
Inputs
S1 (probe 1) NTC
S2 (probe 2) NTC
DI1
free contact, contact resistance < 10 Ω, closing current 6 mA
S3 (probe 3)
NTC
DI2
free contact, contact resistance < 10 Ω, closing current 6 mA
S4 (probe 4)
NTC
Maximum distance of probes and digital inputs less than 10 m. Note: During installation
keep the power and loads connection separate from probe cables, digital inputs, repeater
display and supervisory system
Fig. 1
Probe type
NTC std.
10 kΩ a 25 °C, range –50T90 °C
measurement error
CAREL
Relay outputs (depending on the model)
model
drilling template
71x29 mm
IRxxxx(E,A)(P,Q,S,U,V,X,Y,Z)xxx
IRxxxx(E,A)(N,R,C,B,A,M,L,T)xxx
IRxxxx(E,A)(N,R,C,B,A,M,L,T)xxx
Fig. 2
IRxxxx(0,L,H)(N,R,C,B,A,M,L,T)xxx
IRxxxx(E,A)(P,Q,S,U,V,X,Y,Z)xxx
IRxxxx(0,L,H)(N,R,C,B,A,M,L,T)xxx
Start-up
Autom.address
insulation in reference to very low
assignment
voltage parts
insulation between the relay outputs
indipendent
if pressed for
if pressed for 1
more than 5
s enters the au-
Connections wire section 0.5 - 2.5 mq max current 12A
s at start-up,
tomatic serial ad-
(*): Relay not suitable for fl uorescent loads (neon lights, ...) that use starters (ballasts) with
starts the
dress assigning
phase-shift capacitors. Fluorescent lamps with electronic control devices or without phase-
default
procedure
shift capacitors can be used, within the operating limits specifi ed for each type of relay.
parameter
The installer has to provide the correct dimensioning of the power supply and cable con-
setting
nection between the instruments and the loads. Depending on the model, the maximum
current in the common terminals 1, 3 or 5 is 12 A. When using the controller at maximum
operating temperature and full load, use cables featuring a maximum operating tempera-
ture of 105 °C at least.
Clock
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Front panel degree of protection
Control pollution status
PTI of the insulating material
Period of electric stress across insulating parts long
Heat and fi re resistance category
Class of protection against voltage surges
Type of disconnection or interruption
Construction of control
Classifi cation according to protection against
electric shock
Max. distance between interface and display
Programming key
Safety standards: compliant with the European
reference standards.
Signals on the display
Icon Function
COMPRESSOR compressor ON
FAN
DEFROST
AUX
ALARM
CLOCK
LIGHT
SERVICE
HACCP
CONTINUOUS
CYCLE
Optional connections
Option codes
Code
Description
IROPZDSP00
remote display interface
IREVXGD000
remote repeater dispaly
IROPZ485S0
RS485 serial board interface with automatic recognition of the polarity +/-
PSOPZPRG00
programming key kit
PSOPZKEY00
parameter programmin key with 12 V batteries
PSOPZKEYA0
parameter programming key external 230 Vac power supply
IROPZKEY00
parameter programming key, extended memory with 12 V batteries
PSTCON0*B0
repeater display connection cables (*: 1= 1,5 m; 3= 3 m; 5= 5m)
Power
3 VA, 25 mA~ max.
6 VA, 50 mA~ max.
3 VA, 300 mA~ /mAdc max.
reinforced, 6 mm clearance, 8 mm
creepage, 3750 V insulation
basic, 3 mm clearance, 4 mm creepage,
1250 V insulation
externally guaranteed by safety transfor-
mer (SELV power supply)
reinforced, 6 mm clearance, 8 mm
creepage, 3750 V insulation
1 °C range –50T50 °C
3 °C range 50T90 °C
EN60730-1
UL873
relay
250 V~
operat.
250 V~
operat.cycles
cycles
R2 (*) 5(1) A
100000 5 A res. 1 FLA
30000
6 LRA C300
R3 (*) 5(1) A
100000 5 A res. 1 FLA
30000
6 LRA C300
R1, R2
8(4)A N.O.
100000 8 A res. 2 FLA
30000
R2, R3,
6(4)A N.C.
12 LRA C300
R4 (*)
2(2)A N.O./N.C.
R1
12(2)A
100000 12 A res. 5 FLA
30000
N.O./N.C.
30 LRA C300
reinforced, 6 mm clearance, 8 mm creepage, 3750 V
insulation
basic, 3 mm clearance, 4 mm creepage, 1250 V
insulation
error at 25 °C ±10 ppm (±5.3 min/year)
error in the temperature range -10T60 °C
-50 ppm (-27 min/year)
-10T60 °C for all versions
<90% r.H. non-condensing
-20T70 °C
<90% r.H. non-condensing
smooth and stiff panel installation with
gasket IP65
2 (normal situation)
printed circuit board 250, insulation 175
category D and category B (UL 94-V0)
category II
1.B relay contacts (micro-disconnection)
incorporated control, electronically
Class II, by appropriate incorporation
10 m
available on all models
Normal operation
ON
OFF
blink
compressor OFF compressor
required
fan ON
fan OFF
fan required
defrost in progress
defrost not
defrost required
required
auxiliary output AUX
auxiliary output
anti-sweat heater
active
AUX not active
function active
delayed external alarm
no alarm present alarms and
(before the expiry of
malfunctions
the time ' A 7')
at least one timed
no timed defrost
clock alarm
defrost has been set
is present
auxiliary output
auxiliary output
anti-sweat heater
LIGHT active
LIGHT not active
function active
no malfunctions malfunction (es.
EEPROM error or
probe fault)
function not enabled function enabled
HACCP alarm
(HA and/or HF)
enabled
function enabled
function not
function required
enabled
IROPZ48500
IROPZKEY**
Serial board interface RS485
Programming key
1
2
IROPZDSP00
Display interface option
How to set the set point (desired temperature value)
Step Action
Eff ect
After 1 second the display will
1
show the current set point
Press
for 1 second
The value on the display will
2
Press
or
increase or decrease
The controller will show the tem-
3
Press
perat. read by the probes again
Another way of changing the set point is to set parameter "St" (see the tables below)
How to access and set parameters
type "F" (FREQUENT, not protected by password)
type "C" (CONFIGURATION, password protected)
Step Action
Eff ect
After 3s the display will
1
show the 1st parameter, "0"
Press
for 3 seconds
(password)
The value on the display will
2
Press
or
increase or decrease.
The display will show "St"
3
(Setpoint)
Press
If the password set is 22 the
display will scroll the list of type
4
"C" parameters (CONFIGURA-
Press
or
TION) otherwise the list of type
"F" parameters (FREQUENT)
The display will show the
5
parameter name
Press
The value on the display will
6
Press
or
increase or decrease
The display will show the
7
parameter name again
Press
Repeat steps 2, 3, 4 &
8
5 for all parameters
required
The controller will display
9
the temperature read by the
Press
for 5
probes again
seconds
For both types of access (type "F" and type "C") there is a timeout (no button on the keypad
pressed for 1 min), the procedure is ended without saving the parameter.
Accessing the parameters divided by functional blocks (allows the user to scroll
the list of parameters in blocks)
Once having accessed the type "F" or "C" parameters (see tables above)
Step Action
Eff ect
The display will show the name
1
of the functional block that the
Press
parameter belongs to
The display will show the name
2
Press
or
of the other functional blocks
The display will show the name
3
of the fi rst parameter in the
Press
functional block selected
Alarms with manual reset:
the alarms with manual reset can be reset by pressing the
Manual defrost:
as well as the automatic defrost function, a manual defrost can be enabled, if the tempera-
ture conditions allow, by pressing the
HACCP function:
ir33+ is compliant with the HACCP standards in force since it allows the monitoring of the
temperature of the stored food.
"HA" alarm = exceeded maximum threshold: up to three HA events are saved (HA, HA1,
HA2) respectively from the more recent (HA) to the oldest (HA2) and a HAn signal that di-
splays the number of occurred HA events.
"HF" alarm = power failure lasting over a minute and exceeded AH maximum threshold:
up to three HF events are saved (HF, HF1, HF2) respectively from the more recent (HF) to the
oldest (HF2) and a HFn signal that displays the number of occurred HF events.
HA/HF alarm setting: AH parameter (high temp. threshold); Ad and Htd (Ad+Htd = HACCP
alarm activation delay).
Startup
Display of the details:
access to HA or HF parameters pressing the
glance over.
HACCP alarm erasing:
press the
and
buttons for more than 5 seconds, the message 'res' indicates that the
ON if RTC
alarm have been deleted. To cancel the saved alarms press the
present
more than 5 seconds.
Continuous cycle:
Pressing the buttons
and
simultaneously for more than 3 s enables the continuous
cycle function. During operation in continuous cycle, the compressor continues to operate
for the time 'cc' and it stops when reaches the 'cc' time out or the minimum temperature
envisaged (AL = minimum temperature alarm threshold).
Continuous cycle setting: "cc" parameter (continuous cycle duration): "cc" = 0 never acti-
ve; "c6" parameter (bypassing the alarm after the continuous cycle): "cc" = 0 never active; it
avoids or delays the low temperature alarm after the continuous cycle.
Procedure for setting the default parameter values
To set the default parameter values on the controller, proceed as follows:
1: switch the instrument off ;
2: switch the instrument back on, holding the
on the display.
Note: the default values are only set for the visible parameters (C and F). For further details
see table "Summary of operating parameters".
Fig. 3
Meaning
This the currently active
control set point
Set the desired value
The set point is modi-
fi ed and saved
Meaning
Access to type "F" param. is
direct without password
Enter the password "22" to
access the type "C" param.
or whatever diff erent value
for the type "F" parameters.
This is the current value of
the Setpoint
Set the desired value
This is the current value of
the parameter
Set the desired value
Important: parameters not
yet saved
Important: only now have
all the parameters been
updated
Meaning
Example 'CMP' for the com-
pressor parameters, 'dEF' for
the defrost parameters
Example 'Fan' for the fan
parameters
Example "F0" for 'Fan'
and
for more than 3 s.
button for more than 5 s.
button and use
or
buttons to
+
+
buttons for
button until the message "Std" is shown