Par.
Description
P26
High temperature alarm threshold
if P29=0, P26=0 : threshold disabled
if P29=1, P26=200 : threshold disabled
P27
Alarm diff erential
P28
Alarm delay time
P29
Type of alarm threshold
0=relative; 1=absolute
c29
Digital input 1
0=Input not active
1=Immediate external alarm, automatic reset
2=Immediate external alarm, manual reset
3=Delayed external alarm(P28), manual reset
4=Control ON/OFF in relation to status of digital input
5=Start/stop operating cycle from button
Validity: c0 other than 6,7, & if c33= with "dependence"=16 &
17. With alarm, the status of the relays depends on c31
c30
Digital input 2
See c29
c31
Status of control outputs with alarm from digital input
0= All outputs OFF
1= All outputs ON
2= "Reverse" outputs OFF, others unchanged
3= "Direct" outputs OFF, others unchanged
c32
Serial connection address
c33
Special operation
0=Disabled
1= Enabled
(Before changing, make sure the desired start mode (c0) has
been selected and programmed)
c34
Dependence of output 1
0=output not enabled
1=control output (St1,P1)
2=control output (St2,P2)
3=alarm from digital input (relay OFF)
4= alarm from digital input (relay ON)
5= serious alarms & E04 (relay OFF)
6= serious alarms & E04 (relay ON)
7= serious alarms & E05 (relay OFF)
8= serious alarms & E05 (relay ON)
9= alarm E05 (relay OFF)
10= alarm E05 (relay ON) )
11=alarm E04 (relay OFF) )
12=alarm E04 (relay ON)
13=serious alarm(relay OFF)
14= serious alarm(relay ON)
15=timer
16=control output with change set point & reverse operating
logic from digital input 1
17=control output with change set point & maintain operating
logic from digital input 1
c35
Type of output 1
c36
Activation of output 1
c37
Diff erential/logic of output 1
d34
Activation restriction for output 1
d35
Deactivation restriction for output 1
d36
Minimum value of modulating output 1(*)
d37
Maximum value of modulating output 1(*)
c38
Dependence of output 2
c39
Type of output 2
c40
Activation of output 2
c41
Diff erential/logic of output 2
d38
Activation restriction for output 2
d39
Deactivation restriction for output 2
d40
Minimum value of modulating output 2(*)
d41
Maximum value of modulating output 2(*)
c42
Dependence of output 3
c43
Type of output 3
c44
Activation of output 3
c45
Diff erential/logic of output 3
d42
Activation restriction for output 3
d43
Deactivation restriction for output 3
d44
Minimum value of modulating output 3(*)
d45
Maximum value of modulating output 3(*)
c46
Dependence of output 4
c47
Type of output 4
ir33 universale +030220801 - rel. 1.0 - 16.04.2008
Note Def
Min
Max UoM
150
P25
150
°C/°F
2
0
50
°C/°F
120
0
250
min
1
0
1
-
0
0
5
-
0
0
5
-
0
0
3
-
1
0
207
-
0
0
1
-
1
0
17
-
0
0
1
-
-25
-100
100
%
25
-100
100
%
0
0
3
-
2
0
4
-
0
0
100
%
100
0
100
%
1
0
17
-
0
0
1
-
-50
-100
100
%
25
-100
100
%
1
0
3
-
3
0
4
-
0
0
100
%
100
0
100
%
1
0
17
-
0
0
1
-
-75
-100
100
%
25
-100
100
%
2
0
3
-
4
0
4
-
0
0
100
%
100
0
100
%
1
0
17
-
0
0
1
-
38
Typ. CAREL SVP ModBus®
R/W
A
19
20
R/W
A
20
21
R/W
I
50
123
R/W
D
165
27
R/W
I
51
124
R/W
I
52
125
R/W
I
53
126
R/W
I
54
127
R/W
D
166
28
R/W
I
55
128
R/W
D
167
29
R/W
I
56
129
R/W
I
57
130
R/W
I
58
131
R/W
I
59
132
R/W
I
60
133
R/W
I
61
134
R/W
I
62
135
R/W
D
168
30
R/W
I
63
136
R/W
I
64
137
R/W
I
65
138
R/W
I
66
139
R/W
I
67
140
R/W
I
68
141
R/W
I
69
142
R/W
D
169
31
R/W
I
70
143
R/W
I
71
144
R/W
I
72
145
R/W
I
73
146
R/W
I
74
147
R/W
I
75
148
R/W
I
76
149
R/W
D
170
32
R/W
Icon
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
4
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents