Communications Services - Siemens SINAUT ST7 System Manual

Industrial remote communication - telecontrol
Hide thumbs Also See for SINAUT ST7:
Table of Contents

Advertisement

Properties of the TIM modules

2.2 Communications services

Table 2- 1
Overview of the TIM versions
Can be used in conjunction
S7-300
TIM 3V-IE
TIM 3V-IE
Advanced
TIM 4R-IE
* The TIM can be connected either via the MPI interface of its S7-300 CPU or via its own Ethernet interface to an S7-400 or
to the ST7cc or ST7sc PC.
2.2
Communications services
The following communications services are supported:
Telecontrol communication
Network types
The TIM makes telecontrol communication possible via the following network types:
● Industrial Ethernet
● Dedicated line / wireless network
● Analog dial-up network, ISDN network
● Mobile networks (with the aid of a SCALANCE M router)
– GSM / GPRS (2G)
– UMTS (3G) / HSPA+
– LTE (4G)
● IP-based wireless networks
You will find an overview of the transmission paths and network types in the section
Overview: Connection to LAN / WAN (Page 36).
The "SINAUT ST7" protocol
For telecontrol communication via telecontrol networks the TIM uses the ST7 protocol on the
application layer (OSI layer 7).
32
MPI connec-
with
tion
S7-400
no
no
• *
no
no
Ethernet port
Serial interface
for an external
modem
1
1 (RS-232)
1
1 (RS-232)
2
2
selectable
(RS-232 /
RS-485)
System Manual, 11/2018, C79000-G8976-C178-12
Integrated modem Article number
no
6NH7800-3BA00
no
6NH7800-3CA00
no
6NH7800-4BA00
SINAUT ST7 - Volume 1