Phase
Activity
7
Loading and starting subscriber
management (SubA)
8
Loading and starting LAN-COM
9
Loading and starting subscriber
management (MesA)
10
Loading and starting time-of-day
driver
11
Loading and starting the TD7 soft-
ware of the TIM (TD7onTIM) on
the TIM
12
Loading and starting WAN driver
You can find the LED pattern following a completed or aborted startup in the following table.
Table 4- 5
LED activity on the TIM 4R-IE after a completed or aborted startup
Phase
Status
13
Startup completed or aborted
13a
Startup completed without error
13b
Startup completed with error
13c
Startup aborted, configuration data
missing. TIM expects configuration
data (SDBs).
13d
Startup aborted - No firmware
loaded.
13e
Startup aborted - No SDBs and no
firmware loaded
13f
Default startup completed (see
below)
13g
Automatic default startup complet-
ed (see below)
13h
Startup aborted due to incorrect
firmware (firmware does not match
module type)
The LEDs operate in normal mode
1)
The LEDs remain in the phase in which the error occurred.
2)
Group error LED
If an error occurs during startup, the red group error LED (SF) lights up and, if the TIM is
installed as a CP in an S7-300, a diagnostic interrupt is sent to the CPU. In addition, a
message is entered in the diagnostic buffer of the TIM. In the section on the SINAUT
Diagnostics and Service Tool in Volume 2 of the system manual, you can find all the error
messages that cause the group error LED (SF) to light up.
SINAUT ST7 - Volume 1
System Manual, 11/2018, C79000-G8976-C178-12
SF
RUN
STOP
Off
Flash-
On
es
Off
Flash-
On
es
Off
Flash-
On
es
Off
Flash-
On
es
Off
Flash-
On
es
Off
Flash-
On
es
SF
RUN
STOP
Off
On
Off
On
Off
On
Off
Off
On
Off
Off
On
Off
Off
On
Off
Flash-
Flashes
es
On
Flash-
Flashes
es
On
Flash-
Flashes Flashes Flashes Flashes Flashes Flashes
es
Installation, connecting up, commissioning
4.5 Startup behavior of the TIM modules
KBUS
TXD1
RXD1
Off
On
Off
On
On
Off
Off
Off
On
On
Off
On
Off
On
On
On
On
On
KBUS
TXD1
RXD1
X
X
X
1)
1)
1)
X
X
X
2)
2)
2)
On
Flashes
On
Flashes
On
Flashes
Flashes Flashes Flashes Flashes Flashes
On
On
On
On
On
On
TXD2
RXD2
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
TXD2
RXD2
X
X
1)
1)
X
X
2)
2)
Flashes
On
On
Flashes
On
On
On
On
99