Effects of the default startup
Note
Configuration data is deleted
The TIM is reset to factory settings by forcing a default startup. All configuration data in the
TIM are deleted!
● Deleted data
The following data is deleted by resetting to factory settings:
– Configured IP address of the LAN interface
– All other configuration data in the work memory of the TIM
● Data not deleted
The following data is not deleted by resetting to factory settings:
– MAC addresses of the LAN interfaces
Performing the default startup
To force a default startup, follow the steps outlined below:
1. Turn off the power for the TIM.
2. Press the reset button accessible from the front, turn on the power while holding down the
reset button.
During hardware initialization (LED phase 1), the SF LED is turned off briefly and then
turned on again.
3. Release the reset button at the moment when the RUN LED stops flashing and the SF
LED is turned on again.
4. Wait until the startup of the TIM is completed and the default startup is signaled by the
LEDs.
For the relevant LED patterns see the following section:
– Startup of the TIM 3V-IE variants (Page 96)
– Startup activities of the TIM 4R-IE (Page 98)
SINAUT ST7 - Volume 1
System Manual, 11/2018, C79000-G8976-C178-12
Properties of the TIM modules
2.7 Reset button
49