Technical specifications
5.1 Technical specifications of the TIM 3V-IE variants
Technical specifications - TIM 3V-IE
Work memory required on the S7
CPU
* For details, refer to the catalog IK PI, Cabling Technology
** You can find additional properties and performance data in the section TIM 3V-IE / TIM
3V-IE Advanced (Page 38).
*** The MPI interface of the CPU can also be used with S7-300-CPUs with a partyline, see
section Installing the TIM 3V-IE variants in an S7-300 (Page 61).
Technical specifications of the TIM 3V-IE Advanced
Technical specifications - TIM 3V-IE Advanced
Article number
Attachment to Industrial Ethernet
Quantity
Design
Properties
Standard
Transmission speeds
Permitted cable lengths (Ethernet)
0 ... 55 m
0 ... 85 m
0 ... 100 m
Serial interface for connection to the transmission device
Quantity
Design
Standard
Transmission speeds
Maximum cable length
Power supply
Design
Power supply
104
TD7onCPU
TD7onTIM
6NH7800-3CA00
1 x Fast Ethernet interface (X2)
RJ45 jack, galvanically isolated
Half duplex/full duplex, autocrossover, autonegotiation
100BASE-TX, IEEE 802.3-2005
10 / 100 Mbps
(Alternative combinations per length range) *
Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
Max. 85 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable with
IE FC RJ45 Plug 180
Max. 75 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable +
10 m TP Cord via IE FC RJ45 Outlet
Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
1 x serial interface (X1)
9-pin D-sub male connector, isolated
RS-232
300 to 38400 bps (depending on the connected modem)
6 m
2-pin plug-in terminal strip
Type of voltage
Permitted low limit
Permitted high limit
At least 20 KB; actual requirements depend
on the amounts of data and scope of func-
tions
Best case, 0 bytes
24 VDC
20.4 V
28.8 V
SINAUT ST7 - Volume 1