Parameter 8: PIR Re-Detect Interval Time
In the normal mode, after the PIR motion detected, setting the re-detect time. 8 seconds per tick, default tick is 3 (24 seconds).Setting the suitable value to
prevent received the trigger signal too frequently. Also can save the battery energy.Notice: If this value bigger than the configuration setting NO. 9. There is
a period after the light turned off and the PIR not start detecting.
Size: 1 Byte, Default Value: 3
Setting
1 - 127
Parameter 9: Turn Off Light Time
After turn on the lighting, setting the delay time to turn off the lighting when the PIR motion is not detected. 8 seconds per tick, default tick is 4 (32
seconds).0 means never send turn off light command.
Size: 1 Byte, Default Value: 4
Setting
0 - 127
Parameter 10: Auto Report Battery Time
The interval time for auto report the battery level. 0 means turn off auto report battery.The default value is 12. The tick time can setting by the configuration
No.20.
Size: 1 Byte, Default Value: 12
Setting
0 - 127
Parameter 12: Auto Report Illumination Time
The interval time for auto report the illumination. 0 means turn off auto report illumination.The default value is 12. The tick time can setting by the
configuration No.20.
Size: 1 Byte, Default Value: 12
Setting
0 - 127
Parameter 13: Auto Report Temperature Time
The interval time for auto report the temperature. 0 means turn off auto report temperature.The default value is 12. The tick time can setting by the
configuration No.20.
Size: 1 Byte, Default Value: 12
Setting
0 - 127
Parameter 20: Auto Report Tick Interval
The interval time for auto report each tick. Setting this configuration will effect configuration No.10, No.11, No.12 and No.13.Caution: Setting to 0 means
turn off all auto report function.
Size: 1 Byte, Default Value: 30
Setting
0 - 255
Parameter 21: Temperature Differential Report
The temperature differential to report.0 means turn off this function. The unit is Fahrenheit.Enable this function the device will detect every minutes. And
when the temperature is over 140 degree Fahrenheit, it will continue report.Enable this functionality will cause some issue please see the detail in the
u201cTemperature Reportu201d section.
Size: 1 Byte, Default Value: 1
Setting
0 - 127
Parameter 22: Illumination Differential Report
The illumination differential to report.0 means turn off this function. The unit is percentage.Enable this function the device will detect every minutes. Enable
this functionality will cause some issue please see the detail in the Illumination Report section.
Size: 1 Byte, Default Value: 0
Setting
0 - 99
Disable Multi CC in auto report. (1:Disable, 0:Enable)
Disable to report battery state when the device triggered. (1:Disable, 0:Enable)
Reserve.
Description
PIR Re-Detect Interval Time
Description
Turn Off Light Time
Description
Auto Report Battery Time
Description
Auto Report Illumination Time
Description
Auto Report Temperature Time
Description
Auto Report Tick Interval
Description
Temperature Differential Report
Description
Illumination Differential Report