Hw Installation; Installation Of Nk822X Units; Nk822X Hardware Requirements - Siemens NK8223 Manual For Installation, Configuration And Commissioning

Ethernet port
Table of Contents

Advertisement

HW Installation

5
HW Installation
!
5.1

Installation of NK822x units

5.1.1

NK822x hardware requirements

26
Building Technologies
Fire Safety & Security Products
This section lists the NK8000 hardware installation requirements, and details how
to install them.
There are two possible installation scenarios:
1. Installation of NK822x in an existing cabinet
a. NK822x DIN-rail mounting (typical)
b. Mounting of the NK822x euro-size main board in the control unit housing
of CS11/CS440, CS6 or SI410 using mounting kits (alternative mounting
option if DIN-rail mounting is not possible)
 See the System component list on page 54.
2. Installation of a complete NE8000 cabinet including the NK822x unit
Both scenarios will be discussed in the next sections.
The installation must be carried out by technically qualified personnel.
Environmental requirements
The NK822x units should always be installed in a protective housing, away from
dust, high temperature and humidity, vibrations and impacts. Conditions should
match the specific requirements given in the Technical data section on p.57.
Network requirements
– Ethernet (IEEE 802.3, 10Base-T, half-duplex operation, no auto-sensing or
auto-negotiation, RJ-45 connection
– NK822x requires fixed IP addresses (DHCP not supported)
– Stable network with guaranteed transmission characteristics
(no down-times for maintenance, predictable network load)
NK822x power requirements
Item
Input voltage (DC power supply to NK8225 board)
Power (NK8225 processor board)
Power (fully equipped NK8225)
NK822x housing for DIN-rail mounting
Width
180 mm
Height
108 mm (without connectors)
Depth
80 mm
Weight
0,7 kg (fully equipped)
NK822x main board for internal mounting (CS11, CS6, SI410)
Width
160 mm
Height
100 mm (without connectors)
Depth
Mainboard only: 28 mm
Mainboard + LON: 41 mm
Mainboard + LON + serial add-on: 55 mm
 For the mounting kits for CS11/CS440, CS6, and SI410/SI420 see the System
component list on page 54.
Power supply requirement
10-33 V
DC
6,34 W
8,34 W
007798_g_en NK8000 ICC.doc