Technical data
Power supply requirements
Operating conditions
Dimensions
Weight
Digital Input
Digital Output
Power Supply Supervision
Module
Regulatory Approvals
(CE conformity)
60
Building Technologies
Fire Safety & Security Products
Detailed specifications for LON network:
http://www.echelon.com/Support/documentation/
Section: Engineering Bulletins → Media & Wiring
–
Input voltage (DC power supply to NK8225 board)
–
Power (NK8225 processor board)
–
Power (fully equipped NK8225)
–
NE8001
–
Temperature range
–
Humidity
–
NK8225 boards
–
NK8225 plastic cabinet for DIN-rail
–
NK8225 in NE8001 / wall-mounted
–
NK8225 boards
–
NK8225 plastic cabinet for DIN-rail
–
NK8225 in NE8001
DF8040 8Input Module (max 2 modules)
DF8020 8Output Module (1 module)
DF8090 Power Supply Supervision Module
EN 55022
EN 50130-4
EN 60950-1
10-33 Vdc
6,34 W
8,34 W
100-240 Vac, 50/60Hz,
0 to 50 °C
10 to 95 % non condensing
W x H [mm]
160 x 100 (Euro-size PCB)
W x H x D [mm]
180 x 108* x 80
W x H x D [mm]
385 x 450 x 150
*Excluding connectors
0,35 kg
0,7 kg (fully equipped)
8,5 kg (fully equipped)
Optical coupler Inputs
Max 30Vdc
Relay contacts (NO or NC)
Max 1A at 30 Vdc
Relay lifetime: 100'000 cycles
Supervision of power supply and battery
backup
EMC emission
EMC immunity
LVD (NK822x installed in NE8001)
007798_g_en NK8000 ICC.doc
06.2006