Characteristic
Max. cable length (UTP Cat.4) [m]
Termination
Max. number of nodes per segment
Max. number of repeaters
Polarity insensitive
NK822x has a built-in termination resistor (100Ù) for a doubly terminated bus to-
pology that can be enabled by closing the internal jumper JP6.
 See Fig. 12 p. 21, and section 4.1.6 p. 22.
Please refer to the Echelon Manual for detailed specification on how to set up a LON
network:
http://www.echelon.com/Support/documentation/
Section: Engineering Bulletins → Media & Wiring
CN4: COM 1 RS485 connector
CN4 RS485 connections
Pin
Assignment
1
+ RS485
2
- RS485
COM 1 ... COM 4: RS232 connectors
RS232 lines are connected to 9pin D-Sub connectors, female type
Pin
Assignment
1
CD
2
RXD
3
TXD
4
DTR
5
GND
6
DSR
7
RTS
8
CTS
9
RI
DIN Rail installation
The modules are supplied in a plastic box that can be easily attached to the DIN
rail by hooking it on the top of the rail and pressing it in on the opposite side. To
detach the box, pull downward on the tab located at the rear of the module. The I/O
modules are mounted the same way.
Before removing the box, carefully disconnect the flat cable (bus) of the I
ule, as well as the power supply cables.
2
I
C interface
Fig. 19
Bus topology
1'400
2  100, 1/8W
at each end of segment
2
I
C address settings:
Addr. 8
Addr. 1
(Factory setting)
2
NK822x I
C bus addresses
HW Installation
Free topology
500
1  50, 1/8W
at center of segment
64
4
Yes
2
C mod-
Addr. 2
Addr. 1
29
007798_g_en NK8000 ICC.doc