Troubleshooting - SMC Networks EX510-GMJ1 Operation Manual

Fieldbus system cc-link compatible gw unit
Hide thumbs Also See for EX510-GMJ1:
Table of Contents

Advertisement

Display/ Switch Setting (continued)
Setting of the number of stations occupied
(Switch No.2 to 3)
The setting of the number of stations occupied is performed with
switch No.2 to 3.
3 stations are occupied at shipment.
Station setting
No.2
2 station-occupied
OFF
3 station-occupied
ON
Mode setting (Switch No.4)
Mode setting of each port is available only when 2 stations are
occupied.
No.4 is used for mode setting.
The default setting is mode A.
Mode
No.4
Number of branch
A
OFF
16 points per port
B
ON
8 points per port
22
The max. available number
No.3
of I/O point
ON
Input 32/ Output 32
OFF
Input 64/ Output 64
Valid port
COM A and B
COM A to D

Troubleshooting

Overall system
No.
Item
•Check the power for output (24 VDC) is supplied.
•Check the branch cable is connected to SI unit.
Solenoid
•Check the LED for power supply (PWR) and the
1
valve is not
LED for communication (COM) at SI unit are ON.
working
•Ensure output branch current does not exceed the
specification range.
Valve is not
working as
•Program it after checking the wiring specification
2
program
of manifold block assembly.
directs
Signals
•Check the power for input and controlling GW
cannot be
(24 VDC) is supplied.
3
received
•Check the input unit indication LED is ON.
even with a
•Ensure input branch current does not exceed the
sensor
specification range.
COM A-D is
•Check the connection of UNLIT COM port branch
4
not LIT
to input unit.