Installation
2.3.4
Mounting Horizontal MPH2
on Vertical Frame Member with Aluminum Extrusions
1. Choose a position in the rack for the PDU and install 4 spring nuts into the groove, Figure 2-6.
2. Use a level to check if the horizontal plane is maintained.
3. Set the distance to match the holes on the PDU, and hold the MPH2 PDU over the desired position
(now with the spring nuts).
4. Route the input cable through the rack as desired.
5. Insert screws and use a Torx T30 screwdriver to tighten all of them, Figure 2-6. Leave the screws
slightly loose for the time being.
6. Once all the screws are installed, tighten them completely using 35.4 lb-in (5.2 Nm).

Figure 2-6 Installing horizontal MPH2 in a rack with aluminum extrusions

®
Emerson
MPH2
User Manual
17