Figure 2-2 Re-Assembly To Install An Input Power Cable In Conduit; Table 2-1 Hard-Wired Models-Connection Terminal Ratings - Emerson Network Power MPH2 User Manual

Rack pdu
Hide thumbs Also See for Network Power MPH2:
Table of Contents

Advertisement

Installation
11. Slide the conduit into the conduit connector.
12. Tighten the conduit connector until it grips the conduit and crimps it securely.

Figure 2-2 Re-assembly to install an input power cable in conduit

Number
Description
1
Cover plate
2
Terminal-block screws
3
Terminal blocks
4
Terminal-block labels
Conductor Cross-Section Solid, Minimum
Conductor Cross-Section Solid, Maximum
Conductor Cross-Section Stranded, Minimum
Conductor Cross-Section Stranded, Maximum
Conductor Cross-Section, AWG/kcmil, Minimum
Conductor Cross-Section, AWG/kcmil, Maximum
Conductor Cross-Section Stranded, with Ferrule
without Plastic Sleeve, Minimum
Conductor Cross-Section Stranded, with Ferrule
without Plastic Sleeve, Maximum
Conductor Cross-Section Stranded, with Ferrule
with Plastic Sleeve, Minimum
Conductor Cross-Section Stranded, with Ferrule
with Plastic Sleeve, Maximum
®
Emerson
MPH2
User Manual
Table 2-1
Hard-wired models—Connection terminal ratings
Number
Description
5
Strain-relief collar w/Phillips-head screws
6
Metal end plate (attached with 4 screws)
7
Conduit connector (field-supplied)
8
Conduit (cable not shown)
MPH2 Rating
≤32 A
²
0.2 mm
²
6 mm
²
0.2 mm
4 mm²
24
10
²
0.25 mm
²
4 mm
²
0.25 mm
²
4 mm
13
>32 A
²
0.5 mm
²
16 mm
²
0.5mm
²
10 mm
20
6
²
0.5 mm
²
10 mm
²
0.5 mm
²
10 mm