Emerson Network Power MPH2 User Manual page 36

Rack pdu
Hide thumbs Also See for Network Power MPH2:
Table of Contents

Advertisement

Operation
Level
Settings
User Assigned Label
Asset Tag 1
Asset Tag 2
Overcurrent Alarm Threshold
Overcurrent Warning
Threshold
Undercurrent Alarm Threshold 0
Power Up State
Power On Delay
Power Cycle Delay
Post On Delay
Receptacle
Post Off Delay
Software Over Temperature
Protection (SWOTP)
SWOTP Delay
SWOTP Scope
Criticality
Locked/Unlocked
®
Emerson
MPH2
User Manual
Table 3-1
Factory-default settings (continued)
Default Value
Receptacle
<number>
<empty>
<empty>
95
90
Restore
0
8
0
0
Disabled
10
Local
Critical
Unlocked
Models
Units
Affected
All
Allowed characters include
alphanumeric, space,
All
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
All
%
M,R
Configurable per receptacle.
%
M,R
% calculated from maximum receptacle
current rating on nameplate.
%
M,R
Restore returns receptacle power state
C,R
to last programmed state after expiration
of Power On Delay.
The delay timing begins after
seconds
C,R
measurement stability is achieved.
A Power Cycle turns off power to the
seconds
C,R
receptacle for the specified delay.
Delay before RPC2 issues command to
seconds
C,R
power on receptacle.
Delay before RPC2 issues command to
seconds
C,R
power off receptacle.
• Unconditionally applies regardless of
locked/unlocked and loaded/unloaded
status.
C,R
• At least one temperature sensor is
required.
Delay required for persistent over-
seconds
C,R
temperature alarm condition before
SWOTP triggered.
• Local = affects only PDU connected to
the temperature sensor that triggered
SWOTP.
C,R
• Array = affects all PDUs regardless of
temperature sensor that triggered
SWOTP.
Affects power control when a member of
C,R
a receptacle group.
Affects authorization to manage power
C,R
control and behavior of SWOCP.
31
Notes

Hide quick links:

Advertisement