Simplex 49VO-WRF Instructions page 4

Visible notification appliances, wall mount multi-candela strobes

Advertisement

TrueAlert ES Appliance and IDNAC SLC Controller Compatibility Reference
Compatible Controller and additional
TrueAlert ES Appliances
4100ES with EPS+ or EPS Power Supply
4009 IDNAC Repeater
TrueAlert ES Audible Only (Horns)
TrueAlert ES Audible/Visible
TrueAlert ES Weatherproof
Appliances
TrueAlert ES Strobe Specifications
Electrical Ratings
Typical Operating Voltage Range
Supervisory Requirements
SLC Loading
23 VRMS Current Ratings, for typical design of
IDNAC Addressable SLCs (6 VRMS drop)
General Specifications
Temperature Range
Humidity Range
IDNAC SLC Wiring Specifications
(refer to control panel installation instructions
for more information)
Connections
Installation Instructions
Notes: Refer to compatibility table above for fire alarm control panel and power supply operation type.
TrueAlert ES Strobe LEGACY Compatibility Reference
Compatible Controller
4100ES or 4100U with
TrueAlert Power Supply
4009 TPS, Remote
TrueAlert Power Supply
TrueAlert Addressable
Controller (4009T)
Electrical Ratings Reference for Retrofit Applications
17 VRMS Current Ratings, use when
connected to TrueAlert Addressable SLCs per
above
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code
are trademarks of the National Fire Protection Association (NFPA).
© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Data Sheet
Reference
S4100-0100
S4009-0004
S49AO-0001
S49AV-0001
UL Listed S49WP-0001
ULC Listed S49WP-0002
23 VRMS to 31 VRMS, Special Application (see below for 17 VRMS rating)
1 unit load
Maximum of 63 addresses per SLC, 75 unit loads
Candela Setting
15 cd
47 mA
32 to 122 F (0 to 50 C)
10% to 93%, non-condensing @ 104° F (40° C)
UTP, unshielded twisted pair recommended
Maximum wire length allowed with "T-Taps" for Class B wiring per SLC = 10,000 ft
(3048 m)
Maximum wire length to any appliance = 4000 ft (1219 m)
Maximum wiring resistance between compatible appliances = 26 Ω
Terminal blocks on mounting plate for 18 AWG to 12 AWG (0.82 mm
2
3.31 mm
); two wires per terminal for in/out wiring
579-1031
Data Sheet
Controller Output
Reference
S4100-0031
TrueAlert
S4100-0037
Addressable SLC
S4009-0003
Voltage Range 17 VRMS to 31 VRMS, Special Application
Candela Setting
15 cd
62 mA
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA
www.simplex-fire.com
Controller
IDNAC SLC
Output
Output Voltage
29 VRMS
IDNAC SLC
(regulated)
30 cd
75 cd
110 cd
57 mA
100 mA
132 mA
Available Strobe
Intensity
15, 30, 75, and 110 cd
30 cd
75 mA
Appliance Voltage
Design Reference
23 VRMS
(with 6 VRMS drop)
135 cd
185 cd
160 mA
208 mA
2
to
Appliance Voltage
Minimum
17 VRMS
75 cd
110 cd
133 mA
178 mA
S49VO-0001-3 8/2014