Table 4-4 Fsc-Smm Data Point Configuration Procedure - Honeywell FSC-SM Installation Manual

Safety manager
Table of Contents

Advertisement

4.3
Configuration at TPS Universal Station,
Building FSC-SMM
data points
10/01
This subsection takes you through the general steps for FSC-SMM data
point configuration. To build FSC-SMM data points, you will need to
follow the steps listed in Table 4-4.
For more information refer to Section 4 — Data Point Detailed
Description in the FSC Safety Manager Control Functions.
Information on the definition of a specific parameter can
ATTENTION
be provided to you online by pressing the [HELP] key for the parameter
you have selected.
Table 4-4 – FSC-SMM data point configuration procedure
Step
Once you are in the Process Point Building display, select the
1
FSC-SMM point type you wish to configure.
Enter and select the desired configuration scheme. Use the
2
[PAGE FWD] button on the operator keyboard to move to the next
configuration page as needed.
ATTENTION Data entered should be based on the FSC-SM
Configuration Forms you have filled out.
Press the [F12 LOAD] key to load the data in the FSC-SM database.
3
Press the [F9 WLK BACK] key to return to the Process Point Building
4
display.
Repeat steps 1 to 4 for the next FSC-SMM data point type until all
5
point types are configured.
FSC aliases must be configured before points can be
ATTENTION
downloaded against given aliases.
FSC Safety Manager Installation Guide
Continued
Action
57