Figure 4-5 Us Node-Specific Configuration Display - Honeywell FSC-SM Installation Manual

Safety manager
Table of Contents

Advertisement

4.3
Configuration at TPS Universal Station,
Node-specific
configuration
Figure 4-5 – US Node-Specific Configuration display
PED >>>>>>> POINT:$NM02B13
NODE-SPECIFIC CONFIGURATION
NETWORK NUMBER
NODE NUMBER
NODE TYPE
SM PLATFORM
*****************************************************************
*
WARNING: IF THE POINT MIX OR THE SCAN
*
RATE IS CHANGED, THEN THE NODE'S FULL
*
DATA BASE WILL BE SET TO ITS DEFAULT.
*
THE DISPLAY LINES WHICH CAN CAUSE THE
*
DATA BASE TO BE DEFAULTED ARE STARRED
*
AND HAVE AN ASTERISK (*) IN COLUMN 80.
*
*
*****************************************************************
F1=PED
F2=RECALL DISP
10/01
To configure the node-specific data, return to the NIM Build Type Select
Menu by pressing the [F9 WLK BACK] key (refer back to Figure 4-3).
Select the NODE SPECIFIC CONFIGURATION target. The
Node-Specific Configuration display is shown in Figure 4-5.
Enter and select the desired configuration. Press the [F12 LOAD] key.
Make sure the network and node numbers entered for this
ATTENTION
display match those entered in the UCN Configuration display.
There is no need to configure the redundant FSC-SM device. All
FSC-SM-related information will be automatically transferred to the
"new" primary FSC-SM should there be a failover or switchover to the
backup.
(NTWKNUM)
(NODENUM)
(NODETYP)
(SMPLTFM)
F3=
F5=OVERWRITE
F4=
F6=
FSC Safety Manager Installation Guide
UNIT:SY
02
13
PM
APM
LM
SM
TRICON
FSC
*
*
*
*
*
*
*
*
F7=RECON
F8=PED STATUS
Continued
11 Jun 97 14:05:00
UNENTERED
PAGE 01 OF 03
HPM
F9 =WLK BACK
F11=
F10=WRITE
F12=LOAD
Continued on next page