For Series A Scanner Retrofits
Refer to the illustration on page 10. To eliminate the need to strip the cable back,
follow these steps:
1. Attach the shield wire and a short piece of #20 AWG wire (dotted line) to
the shield lug of the RIO link connector.
2. Attach the other end of the #20 AWG wire to the ring terminal lug.
3. Attach the ring terminal lug to a chassis mounting bracket.
Important: The RIO cable shield must be grounded at the scanner
end only. Ensure that the unshielded portion of the link
communication wire (blue and clear) is as short as
possible.

Specifications

Backplane Current Consumption
Operating Temperature
Storage Temperature
Humidity
Noise Immunity
Agency Certification
Remote I/O Scanner
600 mA at 5V dc
0°C to +60°C (+32°F to +140°F)
-40°C to +85°C (-40°F to +185°F)
5 to 95% without condensation
NEMA Standard ICS 2-230
UL listed / CSA Certified
Class I, Division 2, Groups A,B, C, D
CE marked for all applicable directives
11
Publication 1747-5.33