Required Tools And Equipment - Allen-Bradley 1747-SN Installation Instructions Manual

Remote i/o scanner
Hide thumbs Also See for 1747-SN:
Table of Contents

Advertisement

Baud Rate DIP Switch
The figure below shows the location of the DIP switch and the DIP switch
settings for the supported baud rates.
Important: For proper system operation, the baud rate of all devices
on the RIO link must be the same.
57.6K baud
115.2K baud
230.4K baud
230.4K baud

Required Tools and Equipment

Have the following tools and equipment ready:
• medium blade screwdriver
• termination kit (the package, containing resistors and a ring lug, which was
included with the scanner)
• approximately 38 cm (15 inches) of #20 AWG wire for grounding the drain
shield to the SLC chassis (for Series A retrofits)
• adequate length of RIO communication cable (Belden™ 9463) for your
specific application
Remote I/O Scanner
Publication 1747-5.33
7