8
Remote I/O Scanner

Installation

ATTENTION: Disconnect system power before
!
attempting to install, remove, or wire the module.
Make sure you have set the DIP switch properly before installing the scanner.
Important: Before installation, make sure that your modular SLC
power supply has adequate reserve current capacity. The
scanner requires 600 mA at 5V dc.
Insertion
1. Disconnect power.
2. Align the full-sized circuit board with the chassis card guides. The first slot
(slot 0) of the first rack is reserved for the SLC 500 processor.
3. Slide the module into the chassis until the top and bottom latches catch.
4. Attach the RIO link cable to the connector on the front of the module,
behind the door. Ground the cable's shield wire to a chassis mounting
bracket. Refer to the RIO link wiring illustration on page 10.
Publication 1747-5.33
Card Guide
Cable Tie
Module Release