Cabinet Mounting - WEG CFW-11 Series Installation Manual

Hide thumbs Also See for CFW-11 Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Installation Guide
Do not install heat sensitive components right above the inverter.
NOTE!
The detailed description of all models (IP2X/IP55) of
the CFW-11 frequency inverter is found in the user's
manual, available for download on www.weg.net.

CABINET MOUNTING

Surface assembly:
Provide adequate exhaustion so that the internal cabinet temperature
remains within the allowed range for the inverter operations
conditions.
The power dissipated by the inverter at its rated condition is specified
in
table
A.1, A.2,
A.3
and
A.4
"Dissipated power in Watts – Surface
Mounting".
The cabinet minimum air cooling flow requirements are as shown
in
table
1.
The position and diameter of the mounting holes are according to
figure
1.
A1
a2
øc2
Air flow
a2
a2
øc2
Air flow
Surface mounting
A1
B1
C1
D1
E1
a2
Model
mm
mm
mm
mm
mm
mm
(in)
(in)
(in)
(in)
(in)
(in)
Frame
145
247
227
70
270
115
size A
(5.71)
(9.73)
(8.94)
(2.75)
(10.63)
(4.53)
Frame
190
293
227
71
316
150
size B
(7.48)
(11.53)
(8.94)
(2.78)
(12.43)
(5.91)
Frame
220
378
293
136
405
150
size C
(8.67)
(14.88)
(11.53)
(5.36)
(15.95)
(5.91)
Frame
300
504
305
135
550
200
size D
(11.81)
(19.84)
(12.00)
(5.32)
(21.65)
(7.88)
Frame
335
620
358
168
675
200
size E
(13.19)
(24.41)
(14.09)
(6.61)
(25.57)
(7.88)
Frame
430
1156
360
169
1234
150
size F
(16.93)
(45.51)
(14.17)
(6.65)
(48.58)
(5.91)
Frame
535
1190
426
202
1264
200
size G
(21.06)
(46.85)
(16.77)
(7.95)
(49.76)
(7.87)
Frame
686 1319.7 420.8 171.7 1414 175 1350
size H
Tolerance for d3 and e3: +1.0 mm (+0.039 in)
General tolerance: ±1.0 mm (±0.039 in)
Figure 1: Mechanical installation details
8 | CFW-11
C1
D1
a3
d3
Air flow
Max. 3 mm
øc3
(0.12 in)
a3
d3
øc3
Max. 3 mm
(0.12 in)
Air flow
Flange mounting
b2
c2
a3
b3
c3
d3
e3
f3
mm
mm
mm
mm
mm
M
M
M
(in)
(in)
(in)
(in)
(in)
250
130
240
135
225
M5
M5
M5
(9.85)
(5.12)
(9.45)
(5.32)
(8.86)
300
175
285
179
271
M5
M5
M5
(11.82)
(6.89)
(11.23)
(7.05)
(10.66)
375
195
365
205
345
M8
M6
M6
(14.77)
(7.68)
(14.38)
(8.08)
(13.59)
525
275
517
285
485
M6
M8
M8
(20.67)
(10.83)
(20.36)
(11.23)
(19.10)
650
275
635
315
615
M8
M8
M8
(25.59)
(10.83)
(25.00)
(12.40)
(24.21)
1200
350
1185
391
1146
M10
M10
M8
(47.24)
(13.78)
(46.65)
(15.39)
(45.12)
1225
400
1220
495
1182
M10
M10
M8
(48.23)
(15.75)
(48.03)
(19.49)
(46.53)
M10
595 1345
M10
647 1307
-
D
Ventilation Clearances
A
Model
mm (in)
Frame size A
25 (0.98)
Frame size B
40 (1.57)
Frame size C
110 (4.33)
Frame size D
0142 T2
100 (3.94)
0180 T2
150 (5.91)
0211 T2
Frame size E
0105 T4
100 (3.94)
0142 T4
0180 T4
0211 T4
150 (5.91)
Frame size F
Frame size G
Frame size H
Tolerance: ±1.0 mm (±0.039 in)
Figure 2: Minimum clearance for inverter ventilation
Table 1: Minimun required cabinet cooling air flow
Frame size
Model
All
A
B
All
C
All
D
All
CFW110142T2
CFW110180T2 and 0211T2
CFW110105T4
CFW110142T4
E
CFW110180T4 and 0211T4
CFW110053T6, 0063 T6 and 0080T6
CFW110107T6, 0125T6 and 0150T6
CFW110242T4
CFW110312T4
F
CFW110370T4
CFW110477T4
CFW110170T6, 0216T6 and 0289T6
CFW110515T4, 0601T4 and 0720T4
CFW110760T4
G
CFW110315T6, 0365T6 and 0435T6
CFW110472T6
H
All
Flange mounting:
The losses specified in
table
A.1, A.2,
in Watts - Flange mounting" will be dissipated inside the cabinet. The
remaining losses will be dissipated through the back side.
C
D
B
C
D
mm (in)
mm (in)
mm (in)
25 (0.98)
45 (1.77)
10 (0.39)
30 (1.18)
130 (5.12)
130 (5.12)
40 (1.57)
250 (9.84)
80 (3.15)
130 (5.12)
40 (1.57)
20 (0.78)
250 (9.84)
80 (3.15)
CFM
I/s
m³/min
18
8
0.5
42
20
1.2
96
45
2.7
132
62
3.7
180
95
5.1
265
125
7.5
138
65
3.9
180
95
5.1
265
125
7.5
180
95
5.1
265
125
7.5
250
118
7.1
320
151
9.1
380
180
10.1
460
217
13.0
460
217
13.0
680
321
19.3
1020
481
28.9
680
321
19.3
1020
481
28.9
1100
520
31.2
A.3
and A.4, "Dissipated power

Hide quick links: