CONTROL CONNECTIONS

The control connections (analog inputs/outputs, digital inputs/
outputs), must be made at the CC11 control board terminal strip XC1.
XC1
Terminal Strip
CW
1
REF+
2
AI1+
≥5 kΩ
3
AI1-
4
REF-
CCW
5
AI2+
6
AI2-
rpm
7
AO1
AGND
8
(24 V)
amp
9
AO2
AGND
10
(24 V)
11
DGND*
12
COM
13
24 Vdc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NC1
22
C1
23
NO1
24
NC2
25
C2
26
NO2
27
NC3
28
C3
29
NO3
Figure 24: Signals at connector XC1 - digital inputs working as
"active high"
NOTE!
For changing to "Active Low" remove the jumpers
between XC1:11 and 12, place this jumper between
XC1:12 and 13 and connect common points of the
switches on DI1 to DI6 to XC1:11, instead of XC1:13.
14 | CFW-11
Factory Setting Function
Positive reference for
potentiometer (5.4 V ± 5 %).
Analog input # 1:
Speed reference (remote).
Negative reference for
potentiometer (-4.7 V ± 5 %).
Analog input # 2:
No function.
Analog output # 1:
Speed.
Reference (0 V) for the analog
outputs.
Analog output # 2:
Motor current.
Reference (0 V) for the analog
outputs.
Reference (0 V) for the 24 Vdc
power supply.
Common point of the digital
inputs.
24 Vdc power supply.
Common point of the digital
inputs.
Digital input # 1:
Start / Stop.
Digital input # 2:
Direction of rotation (remote).
Digital input # 3:
No function.
Digital input # 4:
No function.
Digital input # 5:
Jog (remote).
Digital input # 6:
2
nd
ramp.
Digital output #1 DO1 (RL1):
No fault.
Digital output #2 DO2 (RL2):
N > N
- Speed > P0288.
X
Digital output #3 DO3 (RL3):
N* > N
- Speed reference >
X
P0288.
1
XC1
29
Factory Default
DIP-
Signal
Function
switch
Speed reference
AI1
S1.4
(remote)
AI2
No function
S1.3
AO1
Speed
S1.1
AO2
Motor current
S1.2
Figure 25: DIP Switches for setting signal type on analog inputs and outputs
NOTE!
For further information on the Safety Stop function
(STO - Safe Torque Off), refer to the user's manual
available for download on: www.weg.net.
Typical Control Connections
Control connection # 1 - Run/Stop function controlled from the
keypad (Local Mode).
With this control connection, it is possible to run the inverter in local
mode with the factory default settings.
This operation mode is recommended for first-time users, since no
additional control connections are required.
Control connection # 2 - 2-Wire Run/Stop function (Remote Mode).
This wiring example is valid only for the default factory settings and
if the inverter is set to remote mode.
With the factory default settings, the selection of the operation mode
(local/remote) is performed through the HMI key
default). Set P0220 = 3 to change the default setting of HMI key
to remote mode.
Slot 5
Slot 1 (white)
Slot 2 (yellow)
Slot 3 (green)
Slot 4
Factory
Selection
Setting
OFF: 0 to 10 V (factory setting)
OFF
ON: 4 to 20 mA / 0 to 20 mA
OFF: 0 to ±10 V (factory setting)
OFF
ON: 4 to 20 mA / 0 to 20 mA
OFF: 4 to 20 mA / 0 to 20 mA
ON
ON: 0 to 10 V (factory setting)
OFF: 4 to 20 mA / 0 to 20 mA
ON
ON: 0 to 10 V (factory setting)
(local mode is