Omron SYSMAC CV Series Operation Manual page 123

Host link system, unit
Hide thumbs Also See for SYSMAC CV Series:
Table of Contents

Advertisement

Host Link Unit Memory Area Allocations
Contents of CPU Bus Unit System Setup for Port 2
Word: 1500 + (25 x unit number) + 7 to 8
15 14 13 12
+7
Baud rate
15
14 13
bps
0
0
0
9,600
0
0
1
1,200
0
1
0
2,400
0
1
1
4,800
1
0
0
9,600
1
0
1
19,200
1
1
0
Unused
1
1
1
15 14 13 12
+8
15 14 13 12
+9
Port Status
Word: 1500 + (25 x unit number) + 12
15 14 13 12
0
0
0
+12
1: Port 2 host computer is busy.
1: Port 1 host computer is busy.
Number of Errors at Port 1
Word: 1500 + (25 x unit number) + 13
15 14 13 12
+13
11
10
9
8
0
Parity
11 10
0
0
Even number
0
1
Odd number
1
0
No parity
1
1
Stop bits (0: 2 bits; 1: 1 bit)
11
10
9
8
Xoff code
11
10
9
8
Transmission delay time
11
10
9
8
7
0
0
0
0
11
10
9
8
Number of errors at port 1
7
6
5
4
3
2
Unit No.
Data retries (0: no; 1: yes)
Communications method (0: full duplex; 1: half duplex)
Xon/Xoff control (0: no; 1: yes)
Data length (0: 7 bits; 1: 8 bits)
7
6
5
4
3
2
Xon code
7
6
5
4
3
2
6
5
4
3
2
1
0
0
0
0
7
6
5
4
3
2
0
0
Appendix C
Bit
1
0
Bit
1
0
Bit
1
0
Bit
1: Communications port 1 is busy.
1: Communications port 2 is busy.
1: Communications port 1 send is busy.
1: Communications port 2 send is busy.
Bit
1
0
1: FCS error
1: Invalid data
1: Overrun error
1: Framing error
1: Parity error
1: Break detect
121

Advertisement

Table of Contents
loading

Table of Contents