Omron SYSMAC CV Series Operation Manual page 122

Host link system, unit
Hide thumbs Also See for SYSMAC CV Series:
Table of Contents

Advertisement

Host Link Unit Memory Area Allocations
Contents of CPU Bus Unit System Setup for Port 1
Word: 1500 + (25 x unit number) + 2 to 4
15 14 13 12
+2
Baud rate
15
14 13
bps
0
0
0
9,600
0
0
1
1,200
0
1
0
2,400
0
1
1
4,800
1
0
0
9,600
1
0
1
19,200
1
1
0
Unused
1
1
1
15 14 13 12
+3
15 14 13 12
+4
Transmission delay time
120
11
10
9
8
7
0
Parity
11 10
0
0
Even number
0
1
Odd number
1
0
No parity
1
1
Stop bits (0: 2 bits; 1: 1 bit)
11
10
9
8
7
Xoff code
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
Data retries (0: no; 1: yes)
Communications method (0: full duplex; 1: half duplex)
Xon/Xoff control (0: no; 1: yes)
Data length (0: 7 bits; 1: 8 bits)
6
5
4
3
2
1
0
Xon code
6
5
4
3
2
1
0
Appendix C
Bit
Bit
Bit

Advertisement

Table of Contents
loading