B Specifications - Omron SYSMAC CV Series Operation Manual

Host link system, unit
Hide thumbs Also See for SYSMAC CV Series:
Table of Contents

Advertisement

Host Interface Specifications
Communications method
Synchronization method
Baud rate
Transmitted code
Error detection
Interface
Transmission distance
Cable Lengths
RS-232C cable
Total length of RS-422 cable
Length of each RS-422 branch
Optical Connections
Cable
Units with "P" in suffix
APF
20 m
PCF
200 m
Appendix B
Specifications
Four-wire, half duplex
Start-stop, 1 or 2 stop bits (set in PC Setup)
1200/2400/4800/9600/19200 bps (set in PC Setup)
7- or 8-bit ASCII (set in PC Setup)
Vertical parity, even/odd/none (set in PC Setup), FCS (frame check sequence)
RS-232C/RS-422 (set on selector on CPU)
RS-232C: 15 m max.; RS-422: 500 m total max.
(See details under System Configuration.)
15 m max.
500 m max.
10 m max.
Units without "P" in suffix
Connection impossible
800 m
115