FORM QTC3-EG6 (1118)
Unit Dimensions (Cont'd)
(OPTIONAL HEAT
RECOVERY UNIT)
3" VICTAULIC OUTLET
3" VICTAULIC OUTLET
2241.5 [88.25] - FRAME WIDTH
2253.344 [88.71]
OVERALL WIDTH
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;
however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no
higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';
top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
32
QTC3205THE, QTC3225THE
1753.2 [69.03]
1839.5 [72.42]
ORIGIN
194.6 [7.66]
5" VICTAULIC INLET
588.3
[23.16]
1256.1 [49.45]
2061.5 [81.16]
3154.3 [124.18]
4986.1 [196.30]
6459.3 [254.30]
6968.9 [274.37] - FRAME LENGTH
7006.0 [275.83] - OVERALL LENGTH
15.9mm [5/8"] DIA
MOUNTING HOLES (TYP.)
1305.1 [51.38]
1611.6 [63.45]
5" VICTAULIC OUTLET
2938.4 [115.69]
035-24059-017 REV-
POWER ENTRY
330.2 [13.00] WIDE X 177.8 [7.00] HIGH
1177 [46.35]
CONTROL PANEL BOTTOM DETAIL
5" VICTAULIC
INLET
137.5
[5.43]
5" VICTAULIC
OUTLET
QUANTECH
LD26943