4.2.6

Insulation monitoring

In ungrounded low-voltage networks, an insulation monitor is used to monitor the insulation
resistance to ground. This measures the current flowing across an established series
resistor. For this purpose, a measuring voltage is injected into the network against the PE
conductor. If the value falls below an adjustable threshold value for the insulation resistance,
an alarm is output.
Since the network on the DC voltage side is galvanically connected via the parallel
connection of the two partial converters, only one insulation monitor can be used to monitor
the network and DC voltage side for ground faults.
Table 4- 1
Rated network voltage
Up to 690 V
Up to 1000 V
Up to 1300 V
4.3

Commissioning

In principle, all converters should be commissioned as described in the Commissioning
chapter of the SINAMICS DCM DC Converter operating instructions.
The settings in Chapter Additional parameter settings (Page 37) should be made
commissioning. See Chapter Carrying out commissioning (Page 40)
To make the settings, use
● BOP20 operator panel
● AOP30 operator panel: Parameter list
● STARTER commissioning tool: Expert list.
4.3.1

Additional parameter settings

Parameter settings on the master converter and on the slave converter.
Table 4- 2
For 12-pulse series connection of SINAMICS DCM converters:
Parameter
p51799
Mode of operation
p51800
Position in the topology
12-pulse applications
Compact User Manual, 09/2015, A5E34871844H
Possible devices for insulation monitoring:
Type
MR627
IRDH 275/IRDH375
MR627 with MZ611
IRDH 275/IRDH375 with AGH 150W-4
IRDH 275/IRDH375 with AGH 204S-4
Master
0, 41 or 42
41 (Master)
12-pulse series connection
4.3 Commissioning
Manufacturer
AREVA T&D/ALSTOM
BENDER
AREVA T&D/ALSTOM
BENDER
BENDER
before
Slave or parallel devices
The same as on the master
42 (Slave)
43 (devices connected in parallel to
the master)
44 (devices connected in parallel to
the slave)