12-pulse parallel connection
3.2 Configuration
3.2.1

Power increase with parallel connection

In order to increase power, additional SINAMICS DCMs can be connected in parallel.
The options permitted for the parallel connection of SINAMICS DCM devices are described
in the chapters "Parallel connection of additional SINAMICS DCM devices in 6-pulse
operation (Page 14)" and "Parallel connection of additional SINAMICS DCM units in 12-
pulse operation (Page 15)".
3.2.1.1

Parallel connection of additional SINAMICS DCM devices in 6-pulse operation

A maximum of 5 additional SINAMICS DCM devices (M1P1 to M1P5 and S1P1 to S1P5) can
be connected in parallel to the SINAMICS DCM devices of the 12-pulse unit (master M1 and
slave S1) in 6-pulse operation (for details on the 6-pulse parallel connection, see SINAMICS
DCM operating instructions, chapter "Connecting devices in parallel and in series").
The following figure shows an example with one device connected in parallel:
1) Transformer
4) SINAMICS DCM
7) Line reactor
U
= rated voltage of the line supply connected at the converter input
N
I
= direct current of a partial converter (¼ total direct current)
d
Figure 3-4
Explanation of the abbreviations
M1
M1P1
14
2) Overvoltage protection
5) Smoothing reactor
8) Data exchange (12-pulse
parallel connection)
Parallel connection of additional SINAMICS DCM devices in 6-pulse operation
Master, first branch
6-pulse slave of M1
3) Insulation monitoring
6) DC motor
9) Data exchange (6-pulse par-
allel connection)
12-pulse applications
Compact User Manual, 09/2015, A5E34871844H