Monitoring and outputs
June 2016
6.4.1

Modbus registers

Reg#
Meaning
40001
Concentration value as calculated by sensor (RTUsensor_out), Channel 1
40002
Sensor status (RTUsensor_stat), Channel 1
40003
Temperature of sensor element housing in Kelvin (RTU temperature), Channel 1
40004
RFU, Channel 1, always read as 0x0000
40005
RFU, Channel 1, always read as 0x0000
40006
Concentration value as calculated by sensor (RTUsensor_out), Channel 2
40007
Sensor status (RTUsensor_stat), Channel 2
40008
Temperature of sensor element housing in Kelvin (RTU temperature), Channel 2
40009
RFU, Channel 2, always read as 0x0000
40010
RFU, Channel 2, always read as 0x0000
**40021
Transmitter Status
40091
Initialize Quick calibration, channel 1 to 2
40092
Initialize Normal Calibration, channel 1 to 2
40093
Channel 1 high alarm limit
40094
Channel 1 low alarm limit
40095
Channel 2 high alarm limit
40096
Channel 2 low alarm limit
40101
Reset latch relays
RFU – Reserved for future use
** The transmitter Status register (Register 40021) is a bit flag register. The following table shows the detailed meaning
of each bit in the register.
Bit
Meaning
0x0000
Normal Sensor operation – no fault or alarm has happened
0x0001
Channel 1 sensor fault status tripped. Communication Fault, Calibration Fault, etc
0x0002
Channel 1 Low Alarm tripped
0x0004
Channel 1 High Alarm tripped
0x0008
Channel 2 sensor fault status tripped. Communication Fault, Calibration Fault, etc
0x0010
Channel 2 Low Alarm tripped
0x0020
Channel 2 High Alarm tripped
0x0040
Channel 1 needs Calibration
0x0080
Channel 2 needs Calibration
32
NOTE: Alarm points can be set up through Modbus registers 40093 to 40096
Reference Manual
MAN-0076, Revision 09
Readable
Writeable
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X