Connection Diagram - ABB EQmatic Product Manual

Energy analyzer m-bus/modbus
Table of Contents

Advertisement

ABB EQmatic
Device technology

Connection diagram

QA/S 4.xx.1
1
2
3
4
Important
The bus cable must be terminated with resistors (120 Ω, 0.25 W) at both ends so that only minimal
reflections are produced. The serial communication on the RS485 interface operates most efficiently if
the source and load impedance are matched at 120 Ohm. The EOL resistors are connected in parallel
with terminals A and B and are included in the scope of delivery.
U
supply voltage connection
s
RS-485 Modbus slaves/meter connection
Ethernet/LAN connection
ON LED (green)
5
LAN/LINK LED (yellow)
6
Modbus RTU LED
7
Reset button (behind label carrier)
8
Label carrier
QA/S x.yy.1 | 2CDC512090D0202 15