Addressable Device Load Specifications for Battery Standby
Addressable Channel Loading Reference
IDNet 2 Communications Channel Output
IDNAC Communications Channel Output
Block Space Option Card Selection
Note: Refer to diagram on page 2 for Option Module availability. Supervisory and Alarm current specifications are for determining
battery standby requirements.
Single Block Option Modules, Select Three (3) Maximum if No Dual Block Module is Selected;
Select One (1) Maximum if a Dual Block Module or the Module Bracket is Selected
Model
Features
Serial DACT, includes 2, 2080-9047 cables, 14 ft
4010-9912
(4.3 m) long, RJ45 plug and spade lugs
4010-9908
4 Point Aux Relay Module
Voltage Regulator Module, 22.8 to 26.4 VDC
(25 VDC nominal); isolated and resettable output;
4010-9916
includes earth detection circuit and trouble relay for
status monitoring
4010-9918
Dual RS-232 Module
Dual Class A IDNAC Isolator (DCAI); converts a
single Class B IDNAC SLC input to two Class A or
two Class B SLC outputs; provides short circuit
4010-9930
isolation between each Class A or B output circuit;
requires one IDNAC address; the total current
remains controlled by the Class B input source SLC
at 3 A maximum; select up to 2 per IDNAC SLC
BACpac Ethernet Portal Module; requires
4010-9915
4010-9918 RS-232 Module (no address required)
4010-9901
VESDA HLI
Dual Vertical Block (Flat) Modules, Select One, or Two with 4010-9928 Bracket Kit (except for Media Cards)
Model
Features
Dual Vertical Block Card Mounting Kit, allows
4010-9928
selecting two, dual Vertical Block (flat) modules
from the list below
Modular Network Interface Card
4010-9922
(requires two media modules, see below)
4010-9818
Network Media Card Wired
4010-9819
Network Media Card Fiber Optic
4010-9914
Building Network Interface Card
4010-9923*
SafeLINC Internet Interface
4010-9924*
Modem Physical Bridge Class B
4010-9925*
Modem Physical Bridge Class X
4010-9926** TCP/IP Physical Bridge Class B
4010-9927** TCP/IP Physical Bridge Class X
Dual Vertical Block (Slot) Modules, Select One if no Dual Vertical (Flat) Modules from Above are Selected
Model
Features
4010-9920
8 Zone Initiating Device Circuit - Class B
4010-9921
8 Zone Initiating Device Circuit - Class A
*UL, ULC, and CSFM listed.
** FM Approved only.
Supervisory
Device Load
for every 50 Devices
for every 50 Appliances
Option Block Usage
1 Block
(must mount in block D
under ESS)
1 Block
1 Block
1 Block
1 Block
Note: One DCAI module can
be mounted on the ESS
1 Block
1 Block
Option Block Usage
2 Vertical Blocks
2 Vertical Blocks
N/A
(mounts to 4010-9922)
2 Vertical Blocks
2 Vertical Blocks
Requires one of the 2
Vertical Block spaces on the
4010-9928 Mounting Kit
3 Block "L" Shape, requires
one of the 2 Vertical Block
spaces on the 4010-9928
Mounting Kit, plus Block D
Option Block Usage
2 Vertical Blocks
(mother/daughter card)
7
Alarm Current
Current
1 mA per device in alarm; 2 mA
40 mA
per activated device LED
40 mA
calculate per selected appliances
Supervisory
Current
30 mA
15 mA
3 A maximum
with 2.5 A load
60 mA
8.3 mA
123 mA
60 mA
Supervisory
Current
NA
30 mA
55 mA
25 mA
236 mA
115 mA
193 mA
246 mA
196 mA
236 mA
Supervisory
Current
75 mA
S4010-0011-5 11/2015
Alarm
Current
40 mA
60 mA
4.9 A
maximum
with 4 A load
60 mA
18.5 mA
123 mA
60 mA
Alarm
Current
NA
30 mA
55 mA
25 mA
236 mA
115 mA
193 mA
246 mA
196 mA
236 mA
Alarm
Current
195 mA

Advertisement

loading