General Specifications
Input Current
IDNAC SLC Ratings
ESS Power Supply
Output Ratings
IDNAC SLC Wiring
Auxiliary Power Tap
Compatible Special Application
Appliances
Battery Charger
Battery capacity range
Rating (sealed
lead acid
Charger characteristics
batteries)
and performance
Operating Temperature
Environmental
Operating Humidity
Additional
Installation Instructions
Technical
Operating Instructions
Reference
Additional Compatible Equipment and Reference
Subject
4010ES Agent Release Applications and
Accessories
Agent Release Accessories
Building Network Interface
SafeLINC Internet Interface
Interface to VESDA Air Aspiration Detection
Systems
Serial DACT (SDACT)
Fire Alarm Network Overview
TrueInsight Remote Service
4606-9102 Remote LCD Annunciator
Graphic I/O Modules
Remote InfoAlarm Command Center
PC Annunciator
TCP/IP Physical Bridge
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. VESDA is a trademark of Xtralis Pty
Ltd. NFPA 72 and National Fire Alarm and Signaling Code are trademarks of the National Fire Protection Association (NFPA). ASHRAE and BACnet are trademarks of
ASHRAE, American Society of Heating, Refrigeration, and Air Conditioning Engineers.
© 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. 
AC
4 A maximum, 120 VAC @ 60 Hz nominal
Battery
9 A maximum @ 24 VDC (during battery operation)
6 A output for "Special Application" appliances
Note: The 6 A output rating of the ESS was determined
Power Supply
such that optional module currents, and external device
Output Rating
and appliance currents can be directly added together,
not to exceed 6 A total.
3 A, regulated 29 VDC during Alarm, 127 addresses,
139 unit loads; DC-DC converter circuit is >92%
efficient over operating range
Output terminals are rated for 20 to 12 AWG with
duplicate output terminals rated for two wires each,
allowing up to four (4) Class B branch circuit T-taps to
be made in the cabinet; additional T-taps may be made
in external wiring junction cabinets or boxes
2 A maximum, rated 19.1 to 31.1 VDC
Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact
your Simplex product representative for compatible appliances
UL listed for battery charging of 6.2 Ah up to 110 Ah; ULC listed for charging up to
50 Ah batteries; batteries above 33 Ah require separate cabinet
Temperature compensated, dual rate, recharges depleted batteries within 48 hours
per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527
32° to 120°F (0° to 49° C)
Up to 93% RH, non-condensing @ 90° F (32° C) maximum
579-1150
579-969
Data Sheet
S4010-0005
S2080-0010
S4100-0061
S4100-0062
S4100-0026
S2080-0009
S4100-0055
S4100-0063
S4606-0002
S4100-0005
S4010-0008
S4190-0013
S4100-0029
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA
www.simplex-fire.com
Subject
Network Communications
Multi-Signal Fiber Optics
4602 Series SCU/RCU
PC Annunciator
Addressable Device Compatibility, IDNet
Communication Sensors and Devices
4009 IDNAC Repeater
4003EC Voice Control Panel
120 VAC Desktop Remote Printer
110 Ah Batteries and Cabinets
Remote 110 Ah Battery Chargers and Cabinets
BACpac Ethernet Portal Module
Network Physical Bridge
Output switches to
battery backup during
mains AC failure or
brownout conditions
Data Sheet
S4100-0056
S4100-0049
S4602-0001
S4190-0013
S4090-0011
S4009-0004
S4003-0002
S4190-0011
S2081-0012
S4081-0002
S4100-0051
S4100-0057
S4010-0011-5 11/2015